Slide the drawing sideways, or open it full size.
A digital meter draws almost nothing, so it will show volts that are not really there: induced on a long dead wire by a live one beside it, or leaking through a dirty open contact. Eighty volts on a wire you have just isolated is usually this. Switch the meter to its low-impedance setting, or put a test lamp across it, and the phantom disappears; a real voltage does not. The reverse trap exists too: a meter reading zero on a live circuit because a lead is broken, a lead is still in the amps receptacle or the battery is flat, which is why the meter is proved on a known source before and after.
Pocket rule. Strange reading: load the meter. Dead reading: prove the meter.