8.1Source to load: where every fault lives

Slide the drawing sideways, or open it full size.
Source, path, load
Figure 8.1. Source, path, loadOpen full size

Strip any circuit to its skeleton and it is a source, a path and a load. Three questions in order. Is the source there: volts at the breaker, the control transformer, the supply terminals? If not, the fault is upstream and this circuit is innocent of the dead load; but if its own fuse or breaker opened, find out why before you reset it. Is the load good: the coil, the motor, the lamp, meter it alone? If not, change it and ask what killed it. Both good and the thing still dead: something in the path is open or shorted, and the path is a list of suspects you can now walk. Most people start in the middle, at the device that is complaining; the method starts at the ends and squeezes.

Pocket rule. Source, load, then the path between.