Strip any circuit to its skeleton and it is a source, a path and a load. Three questions in order. Is the source there: volts at the breaker, the control transformer, the supply terminals? If not, the fault is upstream and this circuit is innocent of the dead load; but if its own fuse or breaker opened, find out why before you reset it. Is the load good: the coil, the motor, the lamp, meter it alone? If not, change it and ask what killed it. Both good and the thing still dead: something in the path is open or shorted, and the path is a list of suspects you can now walk. Most people start in the middle, at the device that is complaining; the method starts at the ends and squeezes.
Pocket rule. Source, load, then the path between.