The modern fire system is a panel and a handful of loops, each loop a ring of devices with an address, so the panel knows which detector, in which cabin, has operated. Isolators along the loop keep one short from taking the whole loop out; a fault on an addressable loop shows as a range of addresses lost between two isolators, which tells you where to look. The panel has two power supplies and a battery, and a fire alarm also stops ventilation fans, releases the fire doors, closes dampers and, where fitted, starts the local fire-fighting system for that zone; those outputs are the interlocks, and they are why a fire panel fault can stop the engine room fans. The CO2 release is never one of them: that is always a deliberate act by a person at its own cabinet.
What fails: detectors that are dirty, detectors in the wrong place (galley heat near a smoke head), water in a call point or a sounder on deck, a loop cable damaged by somebody's drill, and the battery. A panel in fault is a panel that may not raise an alarm, and class treats it that way; the fault gets fixed or the ship goes to fire patrols.
Pocket rules. Addressable: the lost address range brackets the fault. Dirty heads before loop faults. Water in deck devices. A panel in fault means fire patrols until it is not.
Electrical or mechanical. Panel, loops, devices, battery, power, interlock wiring: electrical. Panel software and the annual service: the fire contractor.