7.4 · (F) A job you do with your handsTroubleshoot a battery charger

Slide the drawing sideways, or open it full size.
A charger, stage by stage
Figure 7.4. A charger, stage by stageOpen full size

A charger is a transformer, a rectifier and a control board that decides the output voltage. Start at the meters on its door: output volts and amps. No output volts (read the charger's own side: with a battery connected the output terminals still show battery volts): input breaker, input fuse, transformer, then the rectifier. Output volts and zero amps with a battery that should be charging: the output fuse, or the battery itself disconnected (with loads on the output too, the charger then carries the load and it is the battery ammeter that reads zero), or a control board that has gone to a fault state. Output volts too high: the control board, or its sense leads, which measure the battery voltage and have come adrift, so the board thinks the battery is low and keeps pushing. Output volts too low: the float setting, the board, or a rectifier with a failed diode, which also makes the output hum louder. A charger alarm is usually the board reporting one of these, and the manual has the code.

Pocket rules. Door meters first. No volts: input side. Volts, no amps: output fuse or the battery. Volts high: sense leads. Volts low and humming: a diode.

Work it

Built for this entry. Lessons first, then the simulator for free play.