Every battery on the ship sits on a charger, and the charger's job is to hold it at float: a voltage just high enough to keep it full without cooking it, about 13.5 V per 12 V lead-acid block, 2.25 V per cell, less when the room is hot. After a discharge the charger goes to boost, a higher voltage for a few hours, then back to float. A charger that never leaves boost boils the battery; one that never reaches float undercharges it; one whose ammeter reads zero with a battery that should be floating has quit. NiCd cells float at about 1.4 V each, against lead-acid's 2.25 V, but a 24 V bank has 19 or 20 of them, so it floats at 27 to 28 V, as high as a lead-acid bank or higher; set the charger for the bank in front of you. They tolerate abuse better; lithium banks are managed by their own electronics and the charger is part of the system.
End of life announces itself in the load test: the voltage under load falls faster and further each time, until one day it falls off a cliff. A bank that still reads the right voltage at rest is not the same as a bank that will carry its load, which is why 7.3 is a load test and not a voltmeter.
Pocket rules. Float voltage per the chemistry and the temperature. Charger ammeter at zero on float: suspect the charger. Boost that never ends boils the bank. Resting voltage proves nothing.
Electrical or mechanical. All electrical.