4.6 · (F) A job you do with your handsReplace a contactor or overload and set the overload

Slide the drawing sideways, or open it full size.
Matching a contactor and setting an overload
Figure 4.6. Matching a contactor and setting an overloadOpen full size

Contactor. Match coil voltage (control voltage, not motor voltage), the main contact rating for a motor load (AC-3 amps, not the resistive figure), and the auxiliary block arrangement. Photograph the wiring. Isolate both the power and the control circuit; they are often fed from different places. Transfer the wires one at a time or by the photo, torque the power lugs, and before you close the door, press the armature in by hand with power off and listen for anything that catches. A contactor that chatters has low control voltage or a cracked shading ring; one that hums has dirt on the pole faces.

Overload. Match the current range so the motor's full-load amps sit in the middle of the dial, and the class to the start: class 10 for a motor that reaches speed in a few seconds, class 20 for a long start like a big fan or a loaded conveyor, class 30 for the hardest starts. Set the dial to the nameplate full-load amps, or nameplate times the service factor on a motor that is allowed to run over. An overload set high to stop nuisance trips is a motor with no protection; find the reason for the trips instead. Check manual versus automatic reset; automatic reset on a three-wire starter is fine, on a two-wire starter it restarts the motor by itself.

Pocket rules. Coil voltage is control voltage. AC-3 rating. Dial to nameplate amps. Class to the start time. Never raise the dial to cure a trip.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 4