After any work that touched the three leads, before you couple the motor to anything that cares which way it turns: a phase-sequence meter on the three leads at the terminal box with them live, or a motor-rotation tester with them dead (turn the shaft by hand and compare with the supply's sequence); compare the arrow with the arrow on the motor frame or the pump casing. Or bump it uncoupled and watch the shaft. A centrifugal pump run backward moves some water and sounds fine, and delivers a fraction of its head, which is how reversed pumps go unnoticed for a watch. A screw pump, a compressor or a fan run backward is noticed faster and sometimes expensively.
To reverse: swap any two of the three leads at the motor terminal box. Not at the starter, because its wiring should keep matching its drawing and the mistake was made at the motor, and not at the switchboard, because then every motor on that feeder reverses. After a wye-delta starter, be careful: the six leads must be swapped as a matched pair of pairs, a pair in the main contactor's set and the matching pair in the delta contactor's set, or the delta connection ends up wrong; follow the starter's drawing.
Pocket rules. Rotation before you couple. Swap at the motor. Six leads: follow the drawing, not your instinct. A pump that seems weak after motor work was probably reversed.