When a set trips and the one left cannot carry everything, the board sheds load before the remaining set trips too. Preferential trip relays watch generator load or frequency, and when it goes over the line for a few seconds they open the feeders the ship can live without, in stages: galley and accommodation air conditioning first, then reefer groups or cargo ventilation, then more. Essential services, steering, lube oil, cooling water, never shed. On a ship with a PMS the same thing is done in software, usually with a load-dependent start that brings the standby set on before the shed is needed.
Knowing which feeders are on the preferential list is part of knowing the board. When the galley goes dark on a hot day, that is the system working, and the question is why the load went over the line, not why the galley tripped.
Pocket rules. Preferential trip is a symptom, not a fault. Know the stages and what is in each. After a shed, the loads do not come back by themselves; somebody closes them, in order, watching the kW.
Electrical or mechanical. The relays, the setpoints, the feeder list: electrical. Changing the list or the setpoints: only with the go-ahead.