1.8Droop

Why two sets stopped sharing after the AVR change

Slide the drawing sideways, or open it full size.
Governor and AVR droop
Figure 1.8. Governor and AVR droopOpen full size

Where you'll meet it. You replace an AVR on set 2, test it alone, perfect. You parallel it and set 2's ammeter climbs toward the limit while set 1's falls, kW equal. The new AVR's droop CT is wired backward: instead of easing off excitation as reactive load rises, it piles on. Swap the two CT leads at the AVR and the amps come together in front of you. The governor side has the same story when one governor's droop setting has been changed, or the load-share line between electronic governors has gone open: kW stops sharing, and the raise/lower switches have to do by hand what the setting used to do by itself.

The idea. Droop lets the governor allow speed to sag a few percent from no load to full load, and lets the AVR allow voltage to sag a little against kVAR. It is not a defect; it is the thing that lets two sets share a bus without fighting, because a set that takes more than its share slows a little and backs off. Same droop and same setpoint, they share. Isochronous governors hold exact speed and share through a wire between them instead; cut the wire and they fight.

Used in: 2.3, 2.9.

Work it

Built for this entry. Lessons first, then the simulator for free play.

All of Part 1