1.4Three-phase: wye, delta, line, phase, rotation

The voltmeter selector switch

Slide the drawing sideways, or open it full size.
The voltmeter selector
Figure 1.4. The voltmeter selectorOpen full size

Where you'll meet it. You turn the voltmeter selector through its positions. Phase to phase: 450, 450, 450. Phase to ground: 230, 290, 260, and they drift. A new ETO decides the board has a problem. It does not. On an ungrounded system the phase-to-ground voltages are set by nothing but leakage and capacitance, and they wander. Only phase-to-phase means anything, until a ground pins one phase to the hull; then phase-to-ground reads 0, 450, 450 and the lamps go with it. Knowing which readings matter saves you an afternoon.

The idea. Nameplate voltage is between lines. Inside a wye-connected machine each winding sees line voltage over 1.73, about 260 V, which is what the stator insulation and your megger reading live with. In a delta each winding sees full line voltage. Rotation is the order the phases peak in, set by nothing but which conductor goes to which terminal; swap two and every motor downstream runs backward, which is why rotation gets checked after any cable work, every time.

Used in: 2.3, 2.7, 3.6, 4.10.