The four places it hides, and when to worry
Where you'll meet it. Four times, specifically. One: you open a switchboard cubicle to work on a breaker and the breaker is open, so it is safe, except the closing spring is charged and the breaker will close the instant a close command arrives or a finger finds the wrong latch. Discharge the spring and read the indicator before you reach in. Two: you isolate a drive and open the cover; the bus capacitors hold about 620 V for minutes, and the lamp that says so is sometimes burned out. Wait, then meter the bus. Three: you open a feeder to a big pump and the pump keeps spinning for a minute on its own inertia, or because a check valve is passing and the flow is driving it; a spinning motor is a generator and its terminals are live. Prove dead at the motor, not at the breaker. Four: batteries have no off switch. Pull the fuse, cover the terminals, keep the wrench away from the bank.
The idea. 450 V is not low voltage in the sense that matters. A bolted fault on a main switchboard can release enough energy in a cycle to burn through clothing from a meter away, fed by generators that take time to trip. Before you open a cubicle, know where the bus is, whether the springs are charged, and whether there is a capacitor bank in the box. Lock out what can be locked out. The arc-flash label on the board tells you the boundary and the gear; if there is no label, treat it as the worst case the board can make.