Reading the number before you climb the tank
Where you'll meet it. The alarm system says the fresh water tank is 100 percent and rising, at sea, with nobody filling it. Before anyone climbs to the tank, look at the raw signal. If the input reads 21 or 22 mA, the transmitter is not telling you the tank is full; it is telling you it is sick, because transmitters are built to park outside the 4 to 20 range when they fault, most of them above 20 and some just under 4. If it reads 0 mA, a wire is open somewhere and the system should be showing a sensor fault, not a level. If it reads exactly 4 mA and never moves, the transmitter has died at zero or the tank really is empty. The number tells you which job you have before you leave the control room.
The idea. Almost every analog sensor on the ship talks in current, not voltage, because current is the same everywhere in a loop no matter how long the cable. Zero is 4 mA, not 0, so a broken wire reads as a fault instead of a reading of zero. The input card reads the current as a voltage across a resistor, usually 250 ohms, so 1 to 5 V. You can break the loop anywhere and put the meter in series, or read the volts across the resistor without breaking anything.