The fire pump on deck
Where you'll meet it. The emergency fire pump motor sits on deck, and after a week of weather it meggers at 0.8 megohm cold. Under the two-megohm floor, so it does not run until it is dried: heat lamps in the terminal box overnight, or low current through the windings, and next morning it reads 20 megohms. That is a wet motor, and the log entry says so. The other motor in the drawing has fallen from 200 to 5 megohms over six months with no weather story, and that is a winding ending; the number is still legal and the trend is the warning. The third thing in the drawing is what happens when the megger reaches a drive: a 500 V DC test across a VFD's output buys you a new VFD. Disconnect electronics first.
The idea. A megger puts 500 or 1000 V DC across the insulation and reads the leakage in megohms. Moisture, temperature, dirt and age all move it, so the trend is worth more than any one reading, and a log is worth more than a rule of thumb. The rule anyway: the old floor is a megohm per kilovolt plus one, about one and a half megohms for a 450 V machine, and the current IEEE guide asks five megohms of a modern low-voltage winding. This book works to two as the line below which a motor does not run; if your ship's procedures set a higher one, use theirs. Anything falling toward it gets dried out before it gets run.