Most people use two positions on the meter and never find out what the rest are for. Here is the whole dial, each one with the job it does on a ship.
V AC and V DC. The usual. One habit: always test the meter on a known live source before and after you prove something dead. A meter with a broken lead, a lead left in the amps receptacle or a flat battery reads zero on a live bus.
LoZ (low impedance). A normal meter has such high input resistance that a long cable or a dirty contact can show phantom volts, 80 V on a wire that is actually dead. LoZ loads the circuit slightly and makes the phantom disappear. Use it whenever a reading makes no sense, and whenever you are proving dead.
mV. Across a shunt to read current, or across a closed contact under load to see the voltage drop that says the contact is going bad.
Ω (resistance). Dead circuits only. Coil resistance against the nameplate, heater elements, the three windings of a motor against each other (they should match within a few percent; one high is a bad connection, one low is a shorted turn), and the fuse-rating arithmetic from 1.1.
Continuity (the beeper). Fuses, wires end to end, contacts open and closed. Fast, but it only says under a few ohms; it does not say good insulation and it does not say zero.
Diode. The rotating rectifier on the alternator; the diodes in a charger or power supply; the LED in a pilot light. Reads the forward voltage drop one way, open the other.
Capacitance. You will use it more as more ships carry drives, soft starters and single-phase motors. Isolate the circuit, discharge the capacitor through a resistor (never a screwdriver), disconnect at least one lead so you are not reading the circuit around it, and measure. Compare with the printed value: within 10 to 20 percent is a live capacitor; well under is a dying one; zero is open; a reading that will not settle usually means it is leaking. Motor-start and run capacitors on single-phase fans and pumps, the capacitors in a soft starter's bypass, the DC bus bank on a drive, the filter capacitors in a power supply that reboots itself: all of them die quietly and this is how you catch it.
Hz. Confirms the frequency on a bus or at a drive output when the panel meter is suspect.
mA and µA. In series in a 4–20 mA loop; across a loop's test terminals. The one range where the meter's own fuse goes if you touch volts by mistake. The volts ranges are not fused and keep working; the current range reads zero until the fuse is changed.
Temperature. With the thermocouple probe: a bearing, a lug, a transformer, a motor frame. A cheap thermal camera has replaced this for most jobs, but the probe still goes where the camera cannot see.
Min/Max and peak hold. Start a motor and read its inrush; watch a voltage that dips when something else starts; catch an intermittent that only shows for a moment. Set it and walk away.
Pocket rules. Prove the meter on a known source first. LoZ when the reading is strange. mA range: check the fuse before you trust a zero. Capacitors: isolate, discharge, disconnect, then measure. CAT III 600 V is the minimum for anything on the switchboard; CAT IV for the generator terminals.