5.10 · (R) Yours: something you are responsible forSolenoid valves, limit switches, proximity sensors

Slide the drawing sideways, or open it full size.
Solenoid, limit switch, prox: proving each
Figure 5.10. Solenoid, limit switch, prox: proving eachOpen full size

These are the ends of the nervous system, where the signal becomes an action or an action becomes a signal, and they fail more than anything else in the loop because they live in the machinery. A solenoid valve is a coil that pulls a plunger; an AC coil burns out when it is held in with the plunger jammed (a DC coil's current does not rise), and the valve sticks when the fluid is dirty. The plug usually has an LED that says volts have reached the plug. The coil can still be burned open, so read the coil off the plug before you call the valve stuck. A limit switch is a mechanical contact operated by the machine; it fails when its roller arm is bent, its cam has slipped, or water has got into the body. A proximity sensor is a solid-state switch that senses metal (inductive) or anything (capacitive) within a few millimeters; it fails when the gap has grown, when it is wired the wrong way round for the input (1.12), or when it has been hit.

Pocket rules. LED on the plug: volts are there. Read the coil off the plug; if it is whole, the valve is stuck. Limit switch: look at the arm and the cam before the contacts. Prox: gap, then wiring, then the sensor. Measure across the coil, not to chassis.

Work it

Built for this entry. Lessons first, then the simulator for free play.

Comes up in

Other entries that send you here.

All of Part 5