Swap a card. Power the rack down if the manual says so; many allow hot swap and some do not. Most cards have a removable terminal block that hinges or unplugs with the wires still on it, so the swap is the block off, the card out, the new card in, the block on, with nothing re-wired. Set any address switches or jumpers to match the old card. Power up, watch the LEDs come back, and check that the channels report correctly on the screen.
Force a point. With the laptop, you can hold an input or output in a state the field does not agree with: force a sensor ON to run a pump whose float switch has failed, force an output OFF to hold something off for a test. A force is not isolation: anyone with a laptop or a download can clear it, so hands in machinery need the breaker locked out. It is a jumper in software, and it has the same risks: a forced point left behind is a machine doing something nobody expects. Forces are logged by the PLC and shown on the CPU; clear every one before you walk away, and write it in the log while it is in.
Back up and restore. Before you touch anything, upload the program from the PLC to the laptop and save it with the ship, the system and the date in the file name. Keep one copy on the laptop, one on the ship's drive, one away from the ship. Restore is the reverse and is the thing that turns a dead CPU into a working one in an afternoon instead of a month.
Pocket rules. Terminal block stays wired. Address switches to match. Forces: log them in, clear them out. Back up before you touch. Three copies.