Three different faults, three different tests, and they get mixed up because people start with the meter instead of the symptom.
The symptom tells you which to test for. A breaker that trips the instant it closes, or a fuse that blows on energizing, is a short: conductor to conductor, or conductor to hull on a grounded system. Lamps uneven or an insulation alarm with everything still running is a ground on an ungrounded system. A load that is simply dead with its breaker closed and its fuses good is an open.
The tests, with the circuit isolated and locked out. For a short: ohms between each pair of conductors; with the motor connected a healthy circuit reads the winding resistance, equal between all three pairs, a few ohms on a small motor and a fraction of an ohm on a big one; a short reads near zero, and the pair that reads low is the pair. On a big motor the windings read so low that you disconnect at the terminal box and test the cable and the motor separately. For a ground on a motor or a power cable: megger each conductor to hull; healthy reads megohms, grounded reads kilohms or less. An ohmmeter is not enough there, because a wet winding can read open on an ohmmeter and fail at 500 V. On a lighting circuit the multimeter on ohms to hull is the test: there is a ground or there isn't. For an open: continuity end to end on each conductor, which means someone at the far end or a jumper between conductors at the far end so you can read a loop from one place.
The ones that fool you. A ground in a motor winding, wye or delta, reads as a ground on all three conductors, because they are connected inside; that is normal, and the cable is not grounded three times. A shorted turn inside a winding reads as one winding a little lower than the other two, not as zero. An open that is intermittent, a cracked conductor in a flexing cable, reads fine on the bench and open on the ship; wiggle the cable while you watch the meter.
Pocket rules. Trips instantly: short, ohm between conductors. Lamps uneven: ground, megger to hull on a motor or cable, ohms to hull on lighting. Dead load: open, continuity end to end. Ohmmeter for shorts and opens, megger for grounds on motors and cables. Wiggle the cable.