DC trips up experienced people because the ship has two kinds of DC system and they behave differently, and because polarity in control circuits does not always mean what the drawing makes it look like.
Two kinds of DC. Switchboard control power and the alarm and automation supply are usually floating: neither pole touches the hull, exactly like the 440 V system, and they have a ground monitor with a positive lamp and a negative lamp. A ground on the positive pole lights one, a ground on the negative lights the other, and like the AC system, one ground does nothing and two is a short. Engine electronics, radios, bridge equipment and anything that came from the automotive or telecom world are negative-grounded: the negative is bolted to chassis on purpose, so a "ground" on that system means the positive has touched metal, which is a dead short and a blown fuse, not a lamp. Know which kind you are standing in front of before you form an opinion about a reading.
Polarity and relay coils. A plain relay coil does not care which way current flows; the drawing may show it switched on the positive side or the negative side, and both work. Where polarity does matter: coils with a built-in flyback diode or LED, PLC inputs and outputs, solenoid valves with electronics in the plug, any sensor. Switched-negative circuits are common on engine and deck machinery, where the positive is permanently on every device and the controller grounds the negative to turn it on. The habit that saves you: before you decide a device is dead, meter it between its own two terminals, not from one terminal to chassis, because on a switched-negative circuit the positive terminal reads 24 V whether the device is on or off.
Finding a DC ground on a floating system. The monitor tells you the pole. Then it is 3.7 again at the distribution fuses: open them one at a time, both poles (a two-pole breaker, or both wires lifted), and watch the lamp, from the circuits most exposed to water inward. The usual culprits: a sensor cable chafed on the engine, a solenoid coil with a cracked case, an indicator lamp holder on deck with water in it, a 24 V floodlight. When the ground is on a long sensor run, split it at the junction boxes. A ground that appears when a device operates is a ground inside that device, in the coil or the output stage.
Finding a DC ground on a chassis-grounded system. It announces itself as a blown fuse or a tripped supply, so the hunt is a short hunt: isolate branches at the fuses, ohm each one positive to chassis with the supply off, and find the one that reads near zero, lower than its load should.
Pocket rules. Floating or chassis-grounded: decide first. Meter across the device, not to chassis. Positive always present does not mean the device is on. Open both poles, watch the lamp. A ground that appears when something operates is inside that something.