2.4 · (R) Yours: something you are responsible forProtective relays and what each one is watching

Slide the drawing sideways, or open it full size.
What each generator relay watches
Figure 2.4. What each generator relay watchesOpen full size

Every generator breaker carries a package of relays, and the fastest way to understand a trip is to know what each relay is looking at. Overcurrent watches amps and trips on a fault or a sustained overload. Reverse power watches the direction of kW and trips when the set is being motored by the bus, protecting the engine from running with no fuel. Undervoltage and overvoltage watch the AVR's work; underfrequency and overfrequency watch the governor's. Differential, on larger sets, compares current entering the stator with current leaving it and trips on the difference, which means a phase-to-phase fault inside the winding. A single ground inside the winding draws almost no current on an ungrounded ship, so differential does not see it; the insulation monitor does. On the switchboard each relay has a flag or a lamp that shows which one operated. Read the flag before you reset anything; the flag is the diagnosis.

Modern boards replace the row of relays with one multifunction relay, and the same logic lives in its menus, with an event log that tells you the order things happened in. Learn to read that log before you need to.

Pocket rules. Reverse power right after closing: incoming set too slow. Overcurrent with no load change: a fault downstream, find it before you re-close. Under-frequency trip on a loaded bus: the engine, not the alternator. Differential: do not re-close; megger the stator first.

Electrical or mechanical. The relays, their test, the flags, the log: electrical. Changing a setting: only with the go-ahead and the coordination study in hand. A relay that fails its test: vendor.