Whose fault is the hunt
Where you'll meet it. The jacket water temperature starts swinging five degrees either side of setpoint the day after the engineers change the three-way valve's positioner. They say the controller has gone bad. Look at the shape of the swing on the trend. A trend that runs flat, jumps, then runs flat again is a valve that sticks and lets go: positioner or packing, their job. A smooth sine wave is a loop with too much gain or too much integral, which is the controller: yours to check, and changed only with the go-ahead. A slow approach that never quite arrives is too little integral. The shape of the swing tells you whose knob it is before anyone touches one.
The idea. A controller compares what it wants with what it has and pushes on the valve or the fuel. Proportional pushes in proportion to the error and settles a little short. Integral keeps pushing while any error remains, removing the offset but able to overshoot and hunt. Derivative pushes against fast change and calms the hunt. You will meet it in governors, boiler controls, temperature valves and the AVR's stability pot, and you will rarely tune one, but you will often be asked whether it is the controller or the valve.