Part II · The Equipment · Family 5 · Power It · Stage 2 · First month

Starters and VFDs

A starter connects a motor to the bus, protects it from slow overload, and lets a push button, a pressure switch, or the automation start and stop it. A variable-frequency drive (VFD) does all of that and also sets the motor's speed by changing the frequency it feeds.

VFD detail: Stage 4

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

LessonWye-Delta StartingA step-by-step lesson on wye-delta starting: why it exists, the six winding ends, the three contactors, setting the timer, what it can't start, and a fault to find.LessonThe Three-Wire StarterBuild a motor starter's control circuit one part at a time, see why it holds itself in and why it stays out after a blackout, then find the fault in a dead one with a meter.LessonThe Nameplate and the OverloadRead the LT pump motor’s plate, clamp its amps against it, link the box for 440 V, work out a painted-over plate, then match a contactor and overload, set the dial and sort five motors that keep tripping.LessonSingle-PhasingThe No. 1 LT pump loses a phase: watch it keep running and fail to restart, see why in the stator field, settle four calls with the clamp meter, and find the open with the ohmmeter.LessonThe VFD from the OutsideThe ER exhaust fan’s drive: rectify, store, chop; the DC bus that outlives the power; the six parameter groups you touch; rotation at the motor leads; six fault logs; and the insulation alarm that comes with the bow thruster.LessonVoltage Drop Across a ContactMeasure across each closed pole of the running LT1 contactor and find the pitted one dropping 14 V, work out the heat, see why it only shows under load, and sort six readings from a panel round.LessonSeries and Parallel: The Pump That Started by ItselfThe No. 2 hold bilge pump’s control rung: the series string, the hold-in and Hand in parallel. Then a pump running with the well dry and one that won’t run, each found with the meter.LessonThe Control SchematicMAC1’s starter on one control schematic: tap the eight loads, read back from the M coil, see what drawn de-energized means when running, find K2’s contacts by name, then find why it won’t start in Auto.LessonThe Bow ThrusterThe biggest motor on the board: whose parts are whose, why it never starts across the line, the start permit (all three sets, lever at zero), megger before the port, and the clamp on the first start.LessonHow Motors BreakPart 4 in one sitting: eight places a motor breaks, ten symptoms sorted to their first check, then three walked on Hawsepiper: hums and won’t turn, trips the breaker on start, runs, stops, runs.LessonDeck Cranes: Hoist, Slew, Luff, Brakes, LimitsDeck crane CR1: whose parts are whose, a crane that cuts out slewed to port, the hoist chain, limits first from the diagnostic page, three valve-coil faults, and six calls.LessonThe Induction Motor: Slip, Starting Current, TorqueWhy the rotor never catches the field, and how to read a motor’s load off a tach when the ammeter is dead. Then six to eight times on start, and torque with the square of the volts.LessonMotor ControllersWhat an across-the-line starter does, start and stop with the seal-in, setting and resetting the overload, reversing with two interlocked contactors on the engine room crane, and the top faults.Simulator · free playFault BenchStarters with a fault you cannot see: operate them, read volts, ohms and amps on any terminal, find the fault, fix it and prove it. Twelve circuits (across-the-line pump, hold bilge pump on floats, wye-delta, a standby pump that starts on low pressure, a starting air compressor with its unloader and trips, and the sewage plant three ways: on floats with its blower, and two timer-run plants; the engine room crane hoist, reversing, with its limits and brake; a generator breaker's closing and tripping circuits in TEST; and an alarm system cabinet with two 4–20 mA loops and two switch inputs; and a hydrophore pump run by a PLC, where the program is your meter) and 250 faults at random.Simulator · free playMotor Starter Fault HuntTroubleshoot a three-phase motor starter with a virtual meter: find where the voltage stops and name the fault.Simulator · free playWye-Delta StarterStart a motor across the line, wye-delta, soft-start or by autotransformer and compare the current, find the fault in a wye-delta starter, and set a purifier’s overload bypass timer.Simulator · free playVariable Frequency DriveInside a VFD: rectifier, DC bus and PWM inverter. See the harmonics a drive puts on a ship’s bus, set one up from a motor nameplate, and work out why it tripped.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Control voltage110 or 220 V AC from a control transformer; 24 V DC on newer boards
Contactor coilpulls in at 85 % of coil voltage or more; drops out somewhere between 75 and 20 %
Overload settingmotor nameplate FLA; 0.58 × FLA when the relay sits in the winding leg of a wye-delta starter
Overload trip classClass 10 trips within 10 s at 7.2 × setting; Class 20 within 20 s
Starting currentAcross the line 6–8 × FLA · wye-delta 2–2.7 × · autotransformer 65 % tap about 3 × · soft starter 2–4 × · VFD 1–1.5 ×
Wye-delta timer5–15 s — after the amps have fallen and leveled
Soft starterinitial voltage 30–50 %; ramp 2–30 s; current limit 300–400 %
VFD DC busabout 1.35 × line volts: 590–620 V DC on a 440–460 V drive
VFD cabinet airunder 40 °C
Pump on a VFD, minimum speed20–30 Hz typical — lube, cooling, and minimum flow set it

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Nothing on start — no lamp, no humControl fuse; control transformer outputFuse; transformer; isolator offReplace the fuse like for like, once. Blows again — find the short
No start from REMOTE or AUTO, LOCAL worksSelector; remote terminalsAutomation signal missing; remote wire; PMS permissiveMeter the remote start terminal
No start from LOCAL, control volts presentE-stops; overload contact; interlocksLatched e-stop or group stop; overload tripped; level or pressure interlock openMeter from the coil back toward the fuse
Pulls in, drops out when start is releasedHolding contact 13–14Auxiliary block loose or worn; wire offFix the auxiliary
Contactor chatters on startControl volts during the startLow control voltage — bus dip, tired transformer, loose coil wireFix the supply; more sets online
Trips at once with a bangFuses; megger motor and cableShort circuit; locked rotorMegger before any reset
Overload trips seconds after a startPhase amps; shaft free?Single-phasing; seized load; brake not releasingFind the cause; one reset only
Overload trips after minutes, every timeRunning amps against plate; setting and classOverloaded; bad bearing; low voltage; wrong settingFind the amps. Never raise the dial
Motor won't stop on the stop buttonContactor by eyeWelded main tipsOpen the isolator or breaker; replace the contactor
Several motors dead togetherWhat they shareGroup e-stop pressed; shared control transformer; feeder breakerLook at what they share before any single starter
Wye-delta motor hums, amps high, pressure lowDelta contactor and timerStuck in wyeStop; fix timer or contactor
Drive RUN lit, Hz on display, amps zeroOutput contactor; motor leadsOutput contactor open; lead off at the motorIsolate and check
Drive overtemperature every afternoonCabinet filters and fansClogged filters; dead fan; hot roomClean; replace the fan