A starter connects a motor to the bus, protects it from slow overload, and lets a push button, a pressure switch, or the automation start and stop it. A variable-frequency drive (VFD) does all of that and also sets the motor's speed by changing the frequency it feeds.
VFD detail: Stage 4
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Control voltage | 110 or 220 V AC from a control transformer; 24 V DC on newer boards |
| Contactor coil | pulls in at 85 % of coil voltage or more; drops out somewhere between 75 and 20 % |
| Overload setting | motor nameplate FLA; 0.58 × FLA when the relay sits in the winding leg of a wye-delta starter |
| Overload trip class | Class 10 trips within 10 s at 7.2 × setting; Class 20 within 20 s |
| Starting current | Across the line 6–8 × FLA · wye-delta 2–2.7 × · autotransformer 65 % tap about 3 × · soft starter 2–4 × · VFD 1–1.5 × |
| Wye-delta timer | 5–15 s — after the amps have fallen and leveled |
| Soft starter | initial voltage 30–50 %; ramp 2–30 s; current limit 300–400 % |
| VFD DC bus | about 1.35 × line volts: 590–620 V DC on a 440–460 V drive |
| VFD cabinet air | under 40 °C |
| Pump on a VFD, minimum speed | 20–30 Hz typical — lube, cooling, and minimum flow set it |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Nothing on start — no lamp, no hum | Control fuse; control transformer output | Fuse; transformer; disconnect off | Replace the fuse like for like, once. Blows again — find the short |
| No start from REMOTE or AUTO, LOCAL works | Selector; remote terminals | Automation signal missing; remote wire; PMS permissive | Meter the remote start terminal |
| No start from LOCAL, control volts present | E-stops; overload contact; interlocks | Latched e-stop or group stop; overload tripped; level or pressure interlock open | Meter from the coil back toward the fuse |
| Pulls in, drops out when start is released | Holding contact 13–14 | Auxiliary block loose or worn; wire off | Fix the auxiliary |
| Contactor chatters on start | Control volts during the start | Low control voltage — bus dip, tired transformer, loose coil wire | Fix the supply; more sets online |
| Trips at once with a bang | Fuses; megger motor and cable | Short circuit; locked rotor | Megger before any reset |
| Overload trips seconds after a start | Phase amps; shaft free? | Single-phasing; seized load; brake not releasing | Find the cause; one reset only |
| Overload trips after minutes, every time | Running amps against plate; setting and class | Overloaded; bad bearing; low voltage; wrong setting | Find the amps. Never raise the dial |
| Motor won't stop on the stop button | Contactor by eye | Welded main tips | Open the disconnect or breaker; replace the contactor |
| Several motors dead together | What they share | Group e-stop pressed; shared control transformer; feeder breaker | Look at what they share before any single starter |
| Wye-delta motor hums, amps high, pressure low | Delta contactor and timer | Stuck in wye | Stop; fix timer or contactor |
| Drive RUN lit, Hz on display, amps zero | Output contactor; motor leads | Output contactor open; lead off at the motor | Isolate and check |
| Drive overtemperature every afternoon | Cabinet filters and fans | Clogged filters; dead fan; hot room | Clean; replace the fan |