Part II · The Equipment · Family 4 · Control It · Stage 1 · Before your first watch

Sensors and Alarm Systems

Sensors turn pressure, temperature, level, and flow into a gauge reading, a contact, or a signal for the alarm and monitoring system. The system decides whether you get a light, a slowdown, or a shutdown, and every alarm means one of two things: the process changed, or the sensor did.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

WorksheetThe Cabinet MapWorksheet. Mark M/V Hawsepiper’s alarm system cabinets and the makers’ controllers on a plan, with what each reads, what feeds it and its network; sort the inhibits and forces into explained and ask-the-Chief; then the twenty alarms from the purifier room. Then fill in and print your own.LessonHow Automation BreaksIs the reading wrong, or the plant? The six checks walked on DG2’s LO pressure over five days, an alarm that won’t clear set beside its limit, three nuisance trends, the first stop for every other symptom, and a dark cabinet traced back up its feed.LessonThe Ship’s NetworksTake a network switch down and see why there are two; measure and fix the resistors on an RS-485 Modbus chain; three silent devices (address, baud, polarity); a switch’s lights for power, cable or a duplicate IP; fiber tested with light; six calls.LessonThe Alarm System as a MapClimb the alarm system from a sensor to the cabin panel; put an unmanned night in order; read an alarm point list; find why an alarm never came (a block signal stuck on); inhibit, un-inhibit and the point someone forgot; where alarm ends and control begins; five calls.LessonTransmitters and SwitchesA number or yes or no; change a pressure transmitter on its valve and vent, and the standby it starts; four tanks where level lies by type; a flow switch that says no flow; set and differential on the air compressor; the path before the loop.LessonThe Loop DrawingDG2’s LO pressure, GE221, on its own loop sheet: follow it from transmitter to card, mark the test points in order, read the scale, half-split a dead loop at the test points, and find a loop with no sheet.LessonThe Alarm Is a SymptomDG1’s HT outlet alarms at 97 °C on two nights: one false, found with the thermometer and a neighbor; one true, walked round the HT circuit to a three-way valve stuck on bypass.LessonDC Grounds: Floating or Chassis-GroundedFloating 110 V and 24 V with + and − lamps, and the EDG engine’s 24 V with its negative on the block: pull breakers, split at junction boxes, meter across the device, hunt a short.LessonThe Nav Sensors and the Feeds Between ThemWho talks to whom through Hawsepiper’s data distributor; read the sentences on a laptop; GPS 1 sending “no fix” traced up its antenna cable; transducer before display; two ECDIS that must match.LessonFive Ways to Talk: Internal CommsHawsepiper’s telephone exchange, PA, talkback, sound-powered phones and general alarm: how each works, what feeds it, what still talks in a blackout, and the two tests nobody else does.LessonUPS Systems: Online, Line-Interactive, BypassUPS-1 under Hawsepiper’s alarm system: its path, battery and bypass, what a line-interactive unit lets through, the loads nobody designed for, and the battery that failed its test.LessonThe Fire Detection Panel: Loops, Addresses, InterlocksWhere Hawsepiper’s fire panel, relay unit, battery and feeds are; addresses on loop B; a drilled cable lost as a range between two isolators; what the panel stops and releases (never the CO₂).LessonEngine Safety: Slowdown and ShutdownThe main engine’s own safety system: its sensors, the slowdown and shutdown lists, the bridge cancel and what it can’t cancel, a 02:10 stop traced to one switch, the test schedule, five calls.LessonThe 4–20 mA Loop: Read It, Find the Break, Prove ItRead the milliamps before you climb the tank, read DG2’s LO pressure loop at every terminal, go card first, half-split a dead tank loop with volts across the pair, prove it with 4, 12, 20 mA.LessonRTDs and Thermocouples: Ohms and MillivoltsDG2’s temperature points sorted into Pt100s and thermocouples; GE224 ohmed against the table at both ends, then found linked as two-wire; No. 4 exhaust low and slow; a new thermocouple fitted.LessonCalibrate or Replace a TransmitterDG2’s LO pressure transmitter has drifted: isolate, vent, take the as-found, chase zero and span until both hold, check the middle. Then pick a replacement that matches all five things.LessonPID: Controller or Valve?The main engine jacket water swings five degrees either side of 85 °C the day after a positioner change. Read the shape of the swing, stroke the valve, and say whether it is the controller or the valve before anyone turns a knob.Simulator · free playRTD and ThermocouplePt100 resistance and lead-wire errors in 2, 3 and 4-wire circuits, type K thermocouples with cold junction and the wrong extension wire, and a temperature sensor fault hunt.Simulator · free playLoop CheckA 4–20 mA loop from supply to card: scale the signal, find the break with a voltmeter, and run a five-point transmitter calibration with as-found and as-left.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
4–20 mA transmitter4 mA = bottom of range · 12 mA = mid · 20 mA = top
4–20 mA loop faultbelow about 3.6–3.8 mA = open circuit · above about 20.5–21 mA = short or over-range
Loop supply24 V DC
PT100 RTD100 Ω at 0 °C · about 138.5 Ω at 100 °C · about 0.385 Ω per °C
Type K thermocoupleabout 0.04 mV per °C above the reference junction
Remote reading vs local gaugewithin a few % of span; a change in the difference is the reading
Alarm delaya few seconds to tens of seconds, set per point
Dead-man timerabout 30 min: local pre-warning, then the bridge a few minutes later

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
High-temperature alarm, local thermometer normalJunction box and terminationsLoose wire; corroded terminal; wet or oily boxTighten and dry before ordering a sensor
Reading jumps to full scale or zero instantlyLoop current or resistanceOpen circuit or short; supply fuseFind the break; the process didn't change that fast
"Sensor fail" or channel faultLoop currentOpen (under 3.8 mA) or short (over 20.5 mA); water in connectorConnector, cable, transmitter, in that order
Plausible reading, steady offsetPart number vs well depth; configured rangeWrong-length element; drift; wrong range in the panelCorrect sensor; recalibrate; check range
Intermittent no-signal alarmTerminal box at the sensorOil or water in the head from a failed O-ring; vibrationOpen, clean, dry, new seal
Several unrelated alarms at onceWhat they shareController, PLC, I/O card, or 24 V supply failingLook at the shared hardware first
Same alarm on two identical machinesWhat they shareCommon OMD panel, control voltage, or supplyFix the shared item; keep a third machine ready
TLI above sounding, worst near the bottomSounding; empty-tank TLI valueDead band; trim; densityReport soundings; record dead bands
TLI and local gauge both high during bunkeringTank ventTank pressurized — vent restricted, fill too fastSlow the fill; clear the vent
Float alarm doesn't come in on testFloat freedom; inhibit listStuck in sludge; switch failed; hold shorter than the delayClean; hold through the delay; replace
Alarm comes and goes, called nuisanceAlarm log; trendA real fault startingWalk to it every time; find it
OMD alarm on one head, engine sounds normalThat head vs the others; bearing temperaturesReal hot spot; dirty lens or sample pipeTreat as real until proven; then clean the head