Sensors turn pressure, temperature, level, and flow into a gauge reading, a contact, or a signal for the alarm and monitoring system. The system decides whether you get a light, a slowdown, or a shutdown, and every alarm means one of two things: the process changed, or the sensor did.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| 4–20 mA transmitter | 4 mA = bottom of range · 12 mA = mid · 20 mA = top |
| 4–20 mA loop fault | below about 3.6–3.8 mA = open circuit · above about 20.5–21 mA = short or over-range |
| Loop supply | 24 V DC |
| PT100 RTD | 100 Ω at 0 °C · about 138.5 Ω at 100 °C · about 0.385 Ω per °C |
| Type K thermocouple | about 0.04 mV per °C above the reference junction |
| Remote reading vs local gauge | within a few % of span; a change in the difference is the reading |
| Alarm delay | a few seconds to tens of seconds, set per point |
| Dead-man timer | about 30 min: local pre-warning, then the bridge a few minutes later |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| High-temperature alarm, local thermometer normal | Junction box and terminations | Loose wire; corroded terminal; wet or oily box | Tighten and dry before ordering a sensor |
| Reading jumps to full scale or zero instantly | Loop current or resistance | Open circuit or short; supply fuse | Find the break; the process didn't change that fast |
| "Sensor fail" or channel fault | Loop current | Open (under 3.8 mA) or short (over 20.5 mA); water in connector | Connector, cable, transmitter, in that order |
| Plausible reading, steady offset | Part number vs well depth; configured range | Wrong-length element; drift; wrong range in the panel | Correct sensor; recalibrate; check range |
| Intermittent no-signal alarm | Terminal box at the sensor | Oil or water in the head from a failed O-ring; vibration | Open, clean, dry, new seal |
| Several unrelated alarms at once | What they share | Controller, PLC, I/O card, or 24 V supply failing | Look at the shared hardware first |
| Same alarm on two identical machines | What they share | Common OMD panel, control voltage, or supply | Fix the shared item; keep a third machine ready |
| TLI above sounding, worst near the bottom | Sounding; empty-tank TLI value | Dead band; trim; density | Report soundings; record dead bands |
| TLI and local gauge both high during bunkering | Tank vent | Tank pressurized — vent restricted, fill too fast | Slow the fill; clear the vent |
| Float alarm doesn't come in on test | Float freedom; inhibit list | Stuck in sludge; switch failed; hold shorter than the delay | Clean; hold through the delay; replace |
| Alarm comes and goes, called nuisance | Alarm log; trend | A real fault starting | Walk to it every time; find it |
| OMD alarm on one head, engine sounds normal | That head vs the others; bearing temperatures | Real hot spot; dirty lens or sample pipe | Treat as real until proven; then clean the head |