The three ground detection lights on a switchboard are connected one to each phase, with their other ends tied together and to the hull. With no ground on the system, all three glow the same, and dimly. When one phase grounds, its lamp goes dark and the other two go bright. The dark lamp is the grounded phase. Nothing trips, because on an ungrounded system one ground is not a short circuit. The lamps are there so the first ground gets found before a second one arrives.
Why the lamps do that
An ungrounded system has no intentional connection between any phase and the hull. The three lamps are connected in wye, and the wye point is tied to the hull. With good insulation everywhere, each lamp sees phase-to-neutral voltage. On a 440 V system that is 440 divided by 1.73, about 254 V. Three equal voltages, three equal lamps.
Now put a solid ground on phase B. Phase B and the hull are the same point, so lamp B has no voltage across it and goes dark. Lamps A and C are now connected from their own phases, through the hull, to phase B. Each has the full 440 V across it, so both are plainly brighter than before.
The motors do not notice. Phase-to-phase voltage has not changed, so everything keeps running. Two things have changed:
- The two good phases now sit 440 V above the hull, not 254 V. Every cable and winding on those phases has more voltage across its insulation.
- A second ground on a different phase is now a phase-to-phase short through the hull. It trips whatever breakers are in its path, and the loads on them stop without warning.
That is the whole case for hunting the first ground while it is still only a lamp.
The test switch
The rule for ungrounded systems (46 CFR 111.05-25) calls for a way to momentarily remove the indicating device from its reference ground. On a lamp set, that is a switch or pushbutton that opens the connection between the lamps and the hull.
With that connection open, the three lamps are a floating wye and must glow equally, whatever the system is doing. That gives you something to compare against. Open the connection and watch:
- Nothing changes. The lamps were already even. No ground is showing.
- One lamp comes up and the other two come down. That phase has a ground on it, even if the difference was hard to see before.
Use it every time the lamps look slightly uneven and you are not sure.
What the lamps miss
Lamps are a coarse instrument. Know where they fail.
- A high-resistance ground. A damp junction box or a tired motor winding leaks a little current to the hull, not enough to pull its lamp down far. The lamps look nearly even. The test switch helps. An insulation monitor that reads in ohms, where one is fitted, shows it clearly.
- Leakage shared across all three phases. If the insulation is poor on every phase by about the same amount, the lamps stay even. Only a monitor reading shows it.
- A burned-out lamp. It looks like a ground at first glance: one dark. But the other two do not go bright. They stay about as they were. Dark with two bright is a ground. Dark with two unchanged is a lamp.
- A lost hull connection. If the lamps' common wire has come off the hull, they glow evenly forever, ground or no ground.
- A ground on a different system. A transformer breaks the path. A ground on the lighting side of a transformer never shows on the 440 V lamps. Each isolated system has its own indication, and the set of lamps that is showing tells you which system to search.
What the rule says
The requirements are in 46 CFR Subpart 111.05.
- Where detection is required (111.05-21). On each electric propulsion system, each ship's service power system, each lighting system, and each power or lighting distribution system that is isolated from ship's service power and lighting by transformers, motor-generator sets or other devices.
- Where the indicators go (111.05-23). At the ship's service generator distribution switchboard for normal power, normal lighting and emergency lighting; at the propulsion switchboard for propulsion systems. They must be readily accessible. For a feeder isolated by a transformer, the indicator may be at the distribution switchboard or at another location such as a centralized monitoring position.
- Ungrounded systems (111.05-25). A suitably sensitive ground detection system at the respective switchboard, giving continuous indication of circuit status to ground, with the test provision described above.
- Grounded neutral systems (111.05-27). A different arrangement: the detection indicates current in the ground connection. The three-lamp reading in this post applies to ungrounded systems.
The rule does not say "lamps." It requires continuous indication. One more number worth knowing: the hull may not be used as a conductor, and one of the listed exceptions is insulation monitoring devices, provided the circulating current does not exceed 30 milliamperes under the most unfavorable conditions (111.05-11).
Finding the ground
The lamps tell you the phase and the system. They do not tell you where. The search is by elimination:
- Read which system's lamps are showing. That rules out every other system.
- Open one circuit at a time on that system and look at the lamps after each. Close it again if nothing changes.
- When the lamps go even, the ground is on the circuit you just opened. Go to its panel and repeat, one branch at a time.
Some loads are not opened to hunt a ground without the go-ahead: steering, propulsion auxiliaries, navigation equipment and fire pumps among them. Start with the circuits that are easy to drop and likely to be wet, such as deck lighting and deck receptacles.
A ground that appears in rain and clears by morning is most likely on deck. Hunt it while it is showing.
Try it
- Ground Lamps and the Ground Hunt: the lamps and the monitor on one switchboard, then a hunt down to a single light fixture.
- Ground Hunt simulator: read the lamps and find the ground breaker by breaker.
- The Ungrounded System: why the first ground trips nothing and the second one does.