9.3The 45 seconds

Slide the drawing sideways, or open it full size.
The 45 seconds, as a timeline
Figure 9.3. The 45 seconds, as a timelineOpen full size

The walk. The emergency generator room and the emergency board, with the drawings from 2.5 and the board's interlock sheet in your hand. Nothing gets operated.

The sheet. A timeline from the moment the bus dies: which relay sees it, what opens, what gives the start signal, which battery cranks, when the breaker closes. Use the real device names from your own sheets. Under the line, two lists: what comes back by itself on the emergency board, and what waits for a person or for the main bus. Then add the main side: which set is on standby, and what the sequential restart brings back, in what order.

When the next blackout test is run, stand at the emergency board with this sheet and a watch, and correct it.

The question. After a blackout the lights are back and one steering pump is not. Is that what the ship is built to do, and what should have restarted it?

Pocket rule. Know what should happen, in order, so you can see the step that did not.

Work it

Built for this entry. Lessons first, then the simulator for free play.

All of Part 9