5.9 · (F) A job you do with your handsSwap an I/O card, force a point, back up and restore

Slide the drawing sideways, or open it full size.
Card swap, force, backup
Figure 5.9. Card swap, force, backupOpen full size

Swap a card. Power the rack down if the manual says so; many allow hot swap and some do not. Most cards have a removable terminal block that hinges or unplugs with the wires still on it, so the swap is the block off, the card out, the new card in, the block on, with nothing re-wired. Set any address switches or jumpers to match the old card. Power up, watch the LEDs come back, and check that the channels report correctly on the screen.

Force a point. With the laptop, you can hold an input or output in a state the field does not agree with: force a sensor ON to run a pump whose float switch has failed, force an output OFF to hold something off for a test. A force is not isolation: anyone with a laptop or a download can clear it, so hands in machinery need the breaker locked out. It is a jumper in software, and it has the same risks: a forced point left behind is a machine doing something nobody expects. Forces are logged by the PLC and shown on the CPU; clear every one before you walk away, and write it in the log while it is in.

Back up and restore. Before you touch anything, upload the program from the PLC to the laptop and save it with the ship, the system and the date in the file name. Keep one copy on the laptop, one on the ship's drive, one away from the ship. Restore is the reverse and is the thing that turns a dead CPU into a working one in an afternoon instead of a month.

Pocket rules. Terminal block stays wired. Address switches to match. Forces: log them in, clear them out. Back up before you touch. Three copies.

Work it

Built for this entry. Lessons first, then the simulator for free play.

LessonSwap a Card, Force a Point, Back Up and RestoreNo. 1 hydrophore pump’s PLC: back up before you touch, swap a dead output card with its block still wired, set a new card’s address, force a failed float and clear it, restore after a flat battery.Simulator · free playFault BenchStarters with a fault you cannot see: operate them, read volts, ohms and amps on any terminal, find the fault, fix it and prove it. Twelve circuits (across-the-line pump, hold bilge pump on floats, wye-delta, a standby pump that starts on low pressure, a starting air compressor with its unloader and trips, and the sewage plant three ways: on floats with its blower, and two timer-run plants; the engine room crane hoist, reversing, with its limits and brake; a generator breaker's closing and tripping circuits in TEST; and an alarm system cabinet with two 4–20 mA loops and two switch inputs; and a hydrophore pump run by a PLC, where the program is your meter) and 250 faults at random.Simulator · free playPLC ProgrammerLearn to write ladder logic from zero. Follow along: twenty-two short guided exercises that tell you exactly what to press, from what a PLC is to contacts, coils, branches, the seal-in, NC wiring, the scan, memory bits, timers, latches, counters, the one-shot, alarm logic, numbers and math, 4–20 mA scaling, an analog alarm with a deadband, a step sequence, and the watch and force tables; skip any you know. Then build it yourself: eleven jobs on the ship's machinery, from a starter and a hold bilge pump to wye-delta, run hours, a hydrophore on a pressure transmitter, tank level alarms with a sensor fault and MAC1's auto start sequence, each checked by tests.Simulator · free playPLC RackSinking and sourcing inputs with PNP and NPN sensors, reading a PLC rack's LEDs to split a fault between field and PLC, and the safe order for swapping a card or forcing a point.