3.4 · (R) Yours: something you are responsible forDC 110 V, 24 V and the control power sources

Slide the drawing sideways, or open it full size.
The two control power trees
Figure 3.4. The two control power treesOpen full size

The switchboard does not control itself from the bus it controls, because on a blackout the bus is dead and the breakers still have to be tripped and closed. So the board has a DC supply, typically 110 V on bigger ships, with a battery and a charger, for trip coils, closing coils, indication and the protective relays. Separately, the alarm and monitoring system, the engine safety system and most of the automation run on 24 V DC, also battery-backed. These two small systems are the nervous system of the plant, and when they fail, the plant can be perfectly healthy and completely blind.

Each has a charger that normally carries the load with the battery floating, and a battery that carries it when the charger or the AC supply is lost. A charger failure shows up days later as a low battery alarm, or on the day of the blackout as nothing working.

Pocket rules. Control power is the first thing to check when everything on a panel is dead at once. Read the charger ammeter: a charger carrying no load with a battery that should be floating is a charger that has quit. Know where the control power fuses are on every board.

Electrical or mechanical. All electrical.