The 440 V plant feeds motors. Lighting, galley, receptacles, electronics and most of the accommodation run on 220 V (or 120 on some ships) through step-down transformers, usually two banks for redundancy, each fed from a different half of the main board. The secondary is a separate ungrounded system with its own ground detection; a ground on the 220 V side does not show on the 440 V lamps and the two hunts are separate.
Transformers are quiet and reliable. What fails is around them: the primary breaker, the secondary breaker, loose connections on the big terminals, and ventilation. A transformer running hot is almost always a transformer with blocked louvers or a load it was not designed for. Check the two banks are sharing if they run in parallel and that the changeover between them works if they do not.
Pocket rules. Two ungrounded systems, two ground hunts. Hot transformer: check the air before you check the windings. Know which half of the main board feeds which bank.
Electrical or mechanical. Transformers, their breakers and their ventilation: electrical. A failed winding: vendor and a spare, which you should know the location of.