Strip the sheath to the depth the gland needs and no further. If the cable is braided, dress the braid evenly into the gland's cone so it is clamped all round; that is the ground continuity for the armor and the electromagnetic screen for signal cables, and a braid left hanging inside the box is neither. Fit the gland and tighten it until the seal grips the sheath; test by a firm pull. Strip the cores to the terminal's length, ferrule stranded conductors, land them, and put the wire numbers on before you close the box, because you will not remember them tomorrow. Leave enough slack inside the box to re-terminate once.
Pocket rules. Braid into the cone, all round. Ferrule every stranded conductor. Number every core before the lid goes on. Slack for one more go.