This is what sets the loop going and holds its speed: starting air turns the engine until it fires, the reversing gear picks the direction, the governor sets the fuel at the inject step, and the control system decides who gives the orders. Its faults show at the worst moment — a start that doesn't come, a slow astern — so most of the work is proving it before you need it.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Starting air at the engine | 25–30 bar; low alarm commonly 15–20 bar |
| Starts from full receivers (class rules) | 12 reversible, 6 non-reversible; compressors refill them from empty in about an hour |
| Air cut-off (firing speed) | Roughly 15–25 % of MCR rpm |
| Remote start attempts | Commonly three, then START FAILED |
| Full ahead to running astern, ship at speed | 1–2 min or more |
| Speed droop, generators in parallel | 3–5 %, equal on every set |
| Generator, full load thrown off | Momentary rise under 10 % |
| Overspeed trip, generator / main engine | 110–115 % of rated / about 110 % of MCR rpm |
| ME hydraulic oil; RT-flex servo / control oil | 200–300 bar; 80–200 / about 200 bar |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| START BLOCKED | Interlock lamps | Turning gear; LO pressure; control position; reversing gear short; shutdown not reset | Clear the cause — never jumper it |
| Won't turn on air, nothing blocked | Manifold pressure | Main start or block valve shut; control air off; start solenoid | Valves; control air; solenoid |
| Turns on air, won't fire | Index during the start | Shutdown not reset; load limit at 0; start limiter low; fuel cold | Reset; load limit up; fuel |
| START FAILED after it fired | Rpm display | Speed pickup dead or gap wrong | Pickup; bottom of the standby order |
| Hunting, or slow to recover | Governor oil; racks | Oil low or aerated; sticky racks; fuel; needle mis-set | Oil, racks, fuel, then compensation |
| Set won't take its share | Droop; mode; raise/lower | Droop unequal; one set isochronous; raise motor dead; load limit | See Generators and AVRs |
| Overspeed on load rejection | Racks free; trip setting | Governor sluggish; linkage sticking at fuel; trip set low | Racks, governor, trip test |
| Keeps turning after STOP | Each rack | Linkage loose — one pump stuck at fuel | Emergency fuel shut-off |
| Rpm short, index on the limiter | Scavenge pressure | Air side fouled; running heavy; limiter signal low | Air side; tell the bridge |
| Slow reversal, air falling | Compressors; gear time | Compressors behind; servomotor slow; leaks | All compressors; bridge in starts |
| Wrong-way alarm | Gear end position | Servomotor short of travel; position switch | Stop; check the gear |