Part II · The Equipment · Family 3 · Heat It or Cool It · Stage 2 · First month

Refrigeration Components

Everything in the refrigeration circuit except the compressor: the valve that meters liquid into the coil, the coil where it boils, the condenser where it turns back to liquid, and the line parts that keep the liquid clean, dry, and where it belongs. Two numbers — superheat and subcooling — tell you what every one of them is doing.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Superheat at the coil outlet5–10 K, the maker's setting
Superheat at the compressor suction10–20 K
Subcooling at the condenser outlet3–8 K
Subcooling at the receiver outletsmall whatever the charge — read the receiver level
Condensing above water outlet / above air on (air-cooled)5–10 K / 10–20 K
Evaporating below room air, provision coils6–10 K
Temperature drop across a filter-drierunder 1–2 K — none you can feel
After defrost: drip time, then fan delay2–5 min, then until the coil is below freezing

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Superheat and suction swinging every few minutesBulb position and clampBulb on a trap, riser, or underneath; valve oversized; superheat set low; equalizer missingMove and insulate the bulb; raise superheat a quarter turn
Superheat high, glass full, subcooling normalValve body for frost; bulb testIce at the orifice; inlet screen blocked; power element dead; set too highWarm the body; clean the screen; renew the element
Superheat high, head low, cold seawaterCondenser water outlet valveHead too low for the valve to feedClose in the water outlet valve
EEV display normal, room warmYour own superheatSensor off the pipe; transducer drift; wrong refrigerant setTransducer against a gauge; refit the sensor
Part of a coil iced after defrostAmps per heater elementElement open; hot gas not reaching that circuitMeter the elements; renew
Water spat into the room or ice on stores after defrostFan delayFans start before the coil refreezesReset the fan delay
Head high, subcooling high, receiver fullCharge recordOvercharge; outlet valve throttledRecover the excess; open the valve
Air-cooled unit head highFins with a torch; fanGrease or lint; fan slow; hot air recirculatingClean the fins; fix the fan; clear the space
Bubbles after the drier, not before; drier sweatingTemperature across itCore blockingChange the drier
Glass clear, line warmer than condensingReceiver level; king valveLine full of gas — charge gone, or king valve shutOpen the valve; leak search before charging
Room satisfied, plant keeps restartingPipe after each solenoidSolenoid passing; manual stem inClean or renew the seat; back out the stem

Draft: this page is drawn from the book manuscript and is still being checked.