Everything in the refrigeration circuit except the compressor: the valve that meters liquid into the coil, the coil where it boils, the condenser where it turns back to liquid, and the line parts that keep the liquid clean, dry, and where it belongs. Two numbers — superheat and subcooling — tell you what every one of them is doing.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Superheat at the coil outlet | 5–10 K, the maker's setting |
| Superheat at the compressor suction | 10–20 K |
| Subcooling at the condenser outlet | 3–8 K |
| Subcooling at the receiver outlet | small whatever the charge — read the receiver level |
| Condensing above water outlet / above air on (air-cooled) | 5–10 K / 10–20 K |
| Evaporating below room air, provision coils | 6–10 K |
| Temperature drop across a filter-drier | under 1–2 K — none you can feel |
| After defrost: drip time, then fan delay | 2–5 min, then until the coil is below freezing |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Superheat and suction swinging every few minutes | Bulb position and clamp | Bulb on a trap, riser, or underneath; valve oversized; superheat set low; equalizer missing | Move and insulate the bulb; raise superheat a quarter turn |
| Superheat high, glass full, subcooling normal | Valve body for frost; bulb test | Ice at the orifice; inlet screen blocked; power element dead; set too high | Warm the body; clean the screen; renew the element |
| Superheat high, head low, cold seawater | Condenser water outlet valve | Head too low for the valve to feed | Close in the water outlet valve |
| EEV display normal, room warm | Your own superheat | Sensor off the pipe; transducer drift; wrong refrigerant set | Transducer against a gauge; refit the sensor |
| Part of a coil iced after defrost | Amps per heater element | Element open; hot gas not reaching that circuit | Meter the elements; renew |
| Water spat into the room or ice on stores after defrost | Fan delay | Fans start before the coil refreezes | Reset the fan delay |
| Head high, subcooling high, receiver full | Charge record | Overcharge; outlet valve throttled | Recover the excess; open the valve |
| Air-cooled unit head high | Fins with a torch; fan | Grease or lint; fan slow; hot air recirculating | Clean the fins; fix the fan; clear the space |
| Bubbles after the drier, not before; drier sweating | Temperature across it | Core blocking | Change the drier |
| Glass clear, line warmer than condensing | Receiver level; king valve | Line full of gas — charge gone, or king valve shut | Open the valve; leak search before charging |
| Room satisfied, plant keeps restarting | Pipe after each solenoid | Solenoid passing; manual stem in | Clean or renew the seat; back out the stem |