One vapor-compression cycle keeps the provisions frozen, the accommodation cool, and the control room electronics inside their limits. The same four parts appear in every unit on the ship; what changes is the size and the box temperature.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Suction — R-404A provision plant, freezer rooms | 0.5–1.5 bar g |
| Suction — R-404A provision plant, cold rooms | 2.5–4 bar g |
| Discharge — R-404A, water-cooled condenser | 14–20 bar g |
| Suction / discharge — R-134a AC plant | 2–3.5 / 8–12 bar g |
| Compressor discharge temperature | 60–90 °C; alarm 110–120 °C |
| Superheat at evaporator outlet | 5–10 K |
| Subcooling at condenser outlet | 3–8 K |
| Condensing temp above cooling water outlet | 5–10 K |
| Meat and fish rooms | −18 to −22 °C |
| Dairy / cold store | +2 to +4 °C |
| Vegetable and fruit room | +4 to +8 °C |
| Freezer defrost | 2–4 per day; ends at coil 10–15 °C |
| Chilled water supply / return | 6–8 °C / 11–13 °C |
| AHU supply air | 12–16 °C |
The plant, stop by stop, as the book walks it.
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Box warm, compressor running continuously | Open the room: coil, fans | Iced coil; fan stopped; low charge; TXV starved; door | Manual defrost; check charge and superheat |
| Box warm, compressor stopped | Which cutout tripped | HP, LP, oil, or overload trip; thermostat; solenoid coil | Find the cause before reset |
| Compressor short-cycling on LP | Receiver level, sight glass | Low charge — leak; solenoid passing; LP setting | Leak search; valve check; reset differential |
| Trips on HP | Cooling water in/out temps | Water flow or temp; fouled tubes; air; overcharge | Restore water; brush tubes; purge |
| Suction line frosted to the compressor | Fans; superheat | TXV overfeeding; fan stopped; bulb loose | Fix fan; bulb; superheat setting |
| Bubbles in the sight glass | Subcooling; drier temperature | Low charge; blocked drier; liquid line heat gain | Charge only if subcooling is low; change drier |
| Moisture indicator wet | Freezer TXV for ice | Moisture — low-side leak, wet charging | Change drier; evacuate if it stays wet |
| Oil level low or foaming, low oil pressure on start | Crankcase heater | Refrigerant in oil — heater off or not on long enough; oil trapped in system | 6 hours of heater before a start; run and watch for return |
| Supply air warm, chilled water warm | Compressor loading; head | Plant capacity; condenser; charge; load | Condenser; charge; shed fresh air |
| One deck hot, others fine | That zone's dampers | Damper moved; fire damper shut; reheater on | Reset dampers; check reheater |
| ECR AC trips on HP during maneuvering | LT temperature; LT cooler ΔP | LT cooler strainer fouling | Switch coolers; reset; clean the offline strainer now |
| AC and provision plants stopped after a blackout | Sequential restart list | Not on the automatic restart | Restart by hand; post the list in the ECR |
Work out what you’d do, then open it.
The meat room has gone from −20 °C to −15 °C over a week. The compressor runs longer every day. No alarms yet. What's happening and how do you find it?
Slow is the clue: nothing has failed outright. Check the receiver level against last week's entry; a drop says leak. If the level is steady, open the room: a coil icing a little more each cycle means a defrost running short — termination thermostat ending early, or one heater element gone so the rest can't finish. A condenser fouling slowly shows as head pressure creeping up each day. The log number that moved tells you where to look.
Arrival maneuvering, and the engine control room AC trips on high pressure. You reset it; it trips again twenty minutes later. What's the connection?
The AC condenser is on the LT central cooling loop. Maneuvering changes the load, and a fouling LT cooler strainer cuts the flow until the warmer LT water pushes the AC head over its cutout. Check the LT cooler ΔP, switch to the other cooler, and reset the AC. Then clean the offline strainer right away — don't wait until the second cooler clogs to clean the first.
The standby generator recovers the bus after a blackout. The vital pumps restart on sequence. Two hours later the cook reports the freezer is warming and the accommodation is hot. What happened?
The AHU fan, the AC compressors, and the provision compressor aren't on the sequential restart; they sat stopped while everyone dealt with the main engine. Restart them by hand — AC first for the control room and switchboard spaces, then provisions. A freezer with its doors shut holds for hours, so the loss is small this time. Write your ship's manual restart list and post it in the ECR so the next blackout includes them.
Draft: this page is drawn from the book manuscript and is still being checked.