A PLC is a small industrial computer that reads switches and sensors, runs a program over and over, and drives relays, solenoids, and lamps. Every automated machine on the ship — purifier, boiler, BWTS, incinerator, power management (PMS), AMS, remote valve system — has one in its cabinet, and when the machine "won't go," the PLC knows why.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Control supply | 24 V DC nominal; most cards accept about 20–29 V |
| 24 V digital input | ON above about 15 V · OFF below about 5 V · between is undefined |
| Analog input | 4–20 mA (see Sensors and Alarm Systems); 0–10 V on some |
| Analog output | 4–20 mA to positioners, I/Ps, and VFD speed references |
| Scan time | a few to tens of milliseconds — faster than anything mechanical |
| CPU battery | 3–3.6 V lithium; 3–5 years; the low warning gives days to weeks |
| CPU LEDs, healthy | RUN steady · ERR/FAULT off · BATT off · FORCE off |
| Cabinet | door shut, fan running, filter clean, no condensation, supply LED steady |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Sequence stops at one step; HMI shows it waiting | The input that step needs; its LED | Switch not made; sensor replaced and never set up; wire off | Make the input real; set up the sensor |
| Output LED lit, device dead | Volts at the card terminal, then at the coil | Blown output fuse; broken wire; interposing relay failed; coil open | Fuse, wire, relay, coil — in that order |
| Output LED off, HMI says it should be on | Permissives in the rung; forces | A permissive missing; a force holding it off | Find the contact that isn't made |
| Input LED lit, field switch open | Junction box; cable | Water in the box; cable shorted to another; wrong terminal after work | Dry and re-terminate |
| Input LED flickering | Voltage at the input with the contact made | Corroded contact dropping volts into the undefined band; loose terminal; supply sagging | Clean the contact; tighten; measure the supply |
| Several unrelated alarms from one controller | What they share; 24 V supply under load | Supply dying; AI card or CPU failing; corroded backplane connector | Supply, then card, then CPU |
| "Communication error", machine runs | Cable and connectors between HMI and PLC | Loose plug; broken shield; temperature-dependent board | Reseat; log the temperature pattern; board if it persists |
| CPU in STOP or FAULT after a power dip | Fault code on the CPU or HMI | Supply fell below the CPU's limit; battery dead and program lost; card fault | Restore supply; reload backup; swap card |
| Machine behaves differently after a power cycle | Parameters against the record | Retained values lost — defaults loaded; clock reset | Reload parameters from the record |
| Automatic sequence runs but skips a step | Drawings against the panel | Wiring modified over years; a jumper or force left in | Compare; remove; redraw |
| A component downstream keeps burning out | What the sequence should do with it | The step that de-energizes it never runs — an input it needs is missing | Fix the sequence input, not the component |