Part II · The Equipment · Family 5 · Power It · Stage 2 · First month

Electric Motors

Nearly every pump, fan, compressor, and purifier on the ship is turned by a three-phase squirrel-cage induction motor fed at 440 V from a starter in an MCC. It has one moving part and two bearings, and it dies from heat, water, and bearings.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

LessonThe Three-Wire StarterBuild a motor starter's control circuit one part at a time, see why it holds itself in and why it stays out after a blackout, then find the fault in a dead one with a meter.LessonMegger a Motor and Dry It OutTest the emergency fire pump motor alone at 500 V for one minute, winding to frame and winding to winding, dry it out without cooking it, and read the curve: wet, ending or faulted.LessonThe Nameplate and the OverloadRead the LT pump motor’s plate, clamp its amps against it, link the box for 440 V, work out a painted-over plate, then match a contactor and overload, set the dial and sort five motors that keep tripping.LessonSingle-PhasingThe No. 1 LT pump loses a phase: watch it keep running and fail to restart, see why in the stator field, settle four calls with the clamp meter, and find the open with the ohmmeter.LessonThe VFD from the OutsideThe ER exhaust fan’s drive: rectify, store, chop; the DC bus that outlives the power; the six parameter groups you touch; rotation at the motor leads; six fault logs; and the insulation alarm that comes with the bow thruster.WorksheetThe Megger LogWorksheet. Write the line (date, frame temperature, one-minute reading), plot five of M/V Hawsepiper’s motors over a year, bring them to the same temperature, and sort the steady, the wet, the falling and the one that only got warm. Then start your own log.LessonGround, Short or Open: Which Do You Have?Let the symptom pick the test: ohms between conductors for a short, the megger to hull for a motor ground (multimeter for lighting), continuity end to end for an open. Then the readings that fool people.LessonRepair a 440 V Motor Cable: The Three-Tape MethodNo. 1 LT pump’s lead cracked at the gland: prove it dead at the motor, find the core, clean it, rubber twice and vinyl over, megger it, fix the gland. Then cooked leads in FOP2’s box.LessonPull a Motor, Fit New Bearings, Line It UpNo. 1 LT pump’s drive-end bearing has gone. Mark it before it comes off, bench-test it, heat new bearings on, run it uncoupled, then align it: soft foot, angular, offset, torque, re-check.LessonThe Bow ThrusterThe biggest motor on the board: whose parts are whose, why it never starts across the line, the start permit (all three sets, lever at zero), megger before the port, and the clamp on the first start.LessonWindlass, Mooring Winches and Hatch CoversMW3, the port aft mooring winch: what is electrical on deck, two speeds and two overloads, a motor that hums against its brake, rain in the control station, and No. 2 hatch cover held by its own limit.LessonHow Motors BreakPart 4 in one sitting: eight places a motor breaks, ten symptoms sorted to their first check, then three walked on Hawsepiper: hums and won’t turn, trips the breaker on start, runs, stops, runs.LessonPhase Rotation: Prove It, Swap It at the MotorNo. 1 ER supply fan bumped backward after its cable was renewed: crossed cores found, two swapped at the motor. Then a reversed LT pump that sounds fine, and SWP1’s six leads by the drawing.LessonAC and Three-Phase: What the Meter Is Telling YouDG2 at 59.3 Hz is an engine running slow. RMS and peak, true-RMS against average-responding on a UPS feed and a drive output, the voltmeter selector, and wye and delta windings.LessonThe Induction Motor: Slip, Starting Current, TorqueWhy the rotor never catches the field, and how to read a motor’s load off a tach when the ammeter is dead. Then six to eight times on start, and torque with the square of the volts.LessonReplacing Motor BearingsThe No. 1 LT pump motor’s drive-end bearing has gone. Mark it before it comes off, pull the old bearings with a puller, match 6311-C3 and 6211-C3, heat the new ones on to about 110 °C, run it uncoupled, then line it up.Simulator · free playThree-PhaseRotating phasors and sine waves, RMS and peak, wye and delta line and phase values with practice problems, and phase rotation: why swapping two leads reverses a motor and three don't.Simulator · free playInduction MotorTorque, current and slip of an induction motor as the load and voltage change, how to read the nameplate and set the overload, and how to prove a single-phased motor.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Supply440 V, 60 Hz, three-phase; 690 V on large plants; 220 V or 120 V single-phase on small gear
Full-load amps (FLA) at 440 Vabout 1.7 A per kW, or 1.25 A per HP — the nameplate rules
No-load amps25–50 % of FLA; higher on small motors
Phase current balancewithin 5 %; above 10 % find out why
Voltage unbalanceunder 2 %; 1 % voltage unbalance makes 6–10 % current unbalance
Slip at full load2–5 %
Starting current, across the line6–8 × FLA for 1–10 s, depending on the load
Starts in successiontwo from cold or one from hot, then wait — maker's figure
Frame temperature at load60–80 °C on a Class F motor; too hot to hold is normal
Bearing housingambient + 20–40 °C
Insulation resistance, 500 V DC1 MΩ floor before starting; healthy tens to hundreds of MΩ
Regreasing interval2,000–4,000 running hours on 4-pole; about half that on 2-pole

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Hums, won't turn, one phase reads zeroFuses; phase amps at the starterSingle-phasing: fuse, contactor tip, loose terminal, broken coreStop; find the open phase; megger before restart
Hums, won't turn, all three phases highShaft free by hand? Brake released?Seized load, jammed pump, brake not releasingStop; free the load
Runs slow, hums, amps high, pump weakStarter transition; bus voltsStuck in wye (see Starters and VFDs); low voltageStop; fix the starter or supply
Trips overload after minutes, every startAmps on three phases; bearings; voltsOverloaded load; dragging bearing; low voltage; wrong settingFind why amps are high. Never raise the setting
Trips breaker or blows fuses at onceMegger motor and cableWinding or cable short; wrong fuse sizeMegger before anything else
Wrong rotation after workArrow on the casing; pump pressureTwo phases swappedSwap any two leads at the motor box
DE bearing hotGrease history; alignment; beltOver- or under-greased; misaligned; belt too tight; bearing failingCorrect grease; realign; plan the bearing
Bearing noisyScrewdriver to the ear; which endBearing failing or dry; fluted race on a VFD motorStop if screaming; change it
Frame hot, amps normalCowl, fins, fan, ambientBlocked cooling; fan broken; ODP choked with dustClean; check the fan
Amps unbalanced over 10 %, volts balancedTerminals; winding resistanceLoose or oxidized terminal; winding fault startingTighten; megger; compare resistances
Megger lowTemperature; what got wet; time stoppedMoisture; dirt and oil; hot winding; failing insulationDry and clean; re-test cold
Amps well below normal on a belt or coupled driveBelt; coupling; primeBelt shredded; coupling sheared; pump lost primeStop — the motor doesn't know its load is gone
Ground alarm when it starts, or water in the boxDrain plugs; gasket; heater; megger motor and cable apartDrains on top; failed gasket; heater off; cable damageIsolate, drain, dry, refit the right way up

Draft: this page is drawn from the book manuscript and is still being checked.