Nearly every pump, fan, compressor, and purifier on the ship is turned by a three-phase squirrel-cage induction motor fed at 440 V from a starter in an MCC. It has one moving part and two bearings, and it dies from heat, water, and bearings.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Supply | 440 V, 60 Hz, three-phase; 690 V on large plants; 220 V or 120 V single-phase on small gear |
| Full-load amps (FLA) at 440 V | about 1.7 A per kW, or 1.25 A per HP — the nameplate rules |
| No-load amps | 25–50 % of FLA; higher on small motors |
| Phase current balance | within 5 %; above 10 % find out why |
| Voltage unbalance | under 2 %; 1 % voltage unbalance makes 6–10 % current unbalance |
| Slip at full load | 2–5 % |
| Starting current, across the line | 6–8 × FLA for 1–10 s, depending on the load |
| Starts in succession | two from cold or one from hot, then wait — maker's figure |
| Frame temperature at load | 60–80 °C on a Class F motor; too hot to hold is normal |
| Bearing housing | ambient + 20–40 °C |
| Insulation resistance, 500 V DC | 1 MΩ floor before starting; healthy tens to hundreds of MΩ |
| Regreasing interval | 2,000–4,000 running hours on 4-pole; about half that on 2-pole |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Hums, won't turn, one phase reads zero | Fuses; phase amps at the starter | Single-phasing: fuse, contactor tip, loose terminal, broken core | Stop; find the open phase; megger before restart |
| Hums, won't turn, all three phases high | Shaft free by hand? Brake released? | Seized load, jammed pump, brake not releasing | Stop; free the load |
| Runs slow, hums, amps high, pump weak | Starter transition; bus volts | Stuck in wye (see Starters and VFDs); low voltage | Stop; fix the starter or supply |
| Trips overload after minutes, every start | Amps on three phases; bearings; volts | Overloaded load; dragging bearing; low voltage; wrong setting | Find why amps are high. Never raise the setting |
| Trips breaker or blows fuses at once | Megger motor and cable | Winding or cable short; wrong fuse size | Megger before anything else |
| Wrong rotation after work | Arrow on the casing; pump pressure | Two phases swapped | Swap any two leads at the motor box |
| DE bearing hot | Grease history; alignment; belt | Over- or under-greased; misaligned; belt too tight; bearing failing | Correct grease; realign; plan the bearing |
| Bearing noisy | Screwdriver to the ear; which end | Bearing failing or dry; fluted race on a VFD motor | Stop if screaming; change it |
| Frame hot, amps normal | Cowl, fins, fan, ambient | Blocked cooling; fan broken; ODP choked with dust | Clean; check the fan |
| Amps unbalanced over 10 %, volts balanced | Terminals; winding resistance | Loose or oxidized terminal; winding fault starting | Tighten; megger; compare resistances |
| Megger low | Temperature; what got wet; time stopped | Moisture; dirt and oil; hot winding; failing insulation | Dry and clean; re-test cold |
| Amps well below normal on a belt or coupled drive | Belt; coupling; prime | Belt shredded; coupling sheared; pump lost prime | Stop — the motor doesn't know its load is gone |
| Ground alarm when it starts, or water in the box | Drain plugs; gasket; heater; megger motor and cable apart | Drains on top; failed gasket; heater off; cable damage | Isolate, drain, dry, refit the right way up |