Part II · The Equipment · Family 5 · Power It · Stage 4 · Moving up

Batteries and UPS

Batteries carry the services that must survive losing the board — emergency generator start, general alarm, radio, emergency lighting, and the automation and navigation fed through a UPS — and a charger keeps them full. A charger holds the bus voltage up whether or not there is a live battery behind it, so the only way to know what you have is to take the charger away and look.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

LessonThe Emergency Generator ChainWatch the undervoltage relay open the tie, start the 250 kW set and close its breaker inside 45 seconds; sort the emergency board’s loads; check cranking volts; run the real test with the tie open and the load on; and name six quiet failures.LessonControl Power: 110 V and 24 V DCThe board’s own 110 V DC supply and the automation’s 24 V: chargers and batteries through a blackout, reading the charger and battery ammeters, a charger that quit two days before anyone noticed, a blown control fuse, and six calls.WorksheetThe Islands and the Control PowerWorksheet. Walk M/V Hawsepiper’s ground lamps and insulation monitors, AC and DC, and note today’s readings; answer four ground alarms from the sheet; fill in the four control supplies; find the dark panel’s fuse. Then fill in and print your own.WorksheetThe Battery RegisterWorksheet. Find all twelve of M/V Hawsepiper’s batteries, from the emergency generator’s starting banks to the boiler controller’s memory cell, and put them on one page; read it for the oldest, the charger showing no current and the banks never tested on load; judge three load-test curves. Then fill in and print your own.LessonDC Grounds: Floating or Chassis-GroundedFloating 110 V and 24 V with + and − lamps, and the EDG engine’s 24 V with its negative on the block: pull breakers, split at junction boxes, meter across the device, hunt a short.LessonGMDSS: The Station, the Radios, the BatteriesHawsepiper’s radio station: every set and what feeds it, the 24 V through a blackout and a dead ship, the three kinds of test, a failed MF/HF test call traced to the aerial, a charger that stopped charging.LessonFive Ways to Talk: Internal CommsHawsepiper’s telephone exchange, PA, talkback, sound-powered phones and general alarm: how each works, what feeds it, what still talks in a blackout, and the two tests nobody else does.LessonUPS Systems: Online, Line-Interactive, BypassUPS-1 under Hawsepiper’s alarm system: its path, battery and bypass, what a line-interactive unit lets through, the loads nobody designed for, and the battery that failed its test.LessonBattery Load Test and ReplacementHawsepiper’s engine room 24 V bank on its real load: CH2 off, logged against August, done at 54 minutes. Then the one low cell, how each bank is tested, and the change, like for like.LessonWatertight Doors, Davits and the Boat BatteryA WT door that shows open on the bridge while it is shut, a davit limit that didn’t stop the hoist, a lifeboat battery dying behind a green davit plug, and a lift’s safety string.LessonTroubleshoot a Battery ChargerHawsepiper’s engine room 24 V charger, CH2, opened up: door meters first, then four faults: a blown input fuse, a latched board and a cooked output fuse, a sense lead adrift, an open diode.LessonHow Hotel Systems BreakPart 7 round-up on Hawsepiper: sort eight calls into water, heat, vibration and neglect; then a UPS alarm, a fire panel fault, a tripping galley GFCI and a machine you have never seen.Simulator · free playBattery ChargerFloat, boost and temperature compensation on a 24 V lead-acid bank, reading cell voltages and specific gravity, and finding out why a charger isn't charging.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Lead-acid float, per cell2.20–2.30 V flooded; 2.25–2.30 V VRLA, compensated down as it gets hotter (a 24 V bank of 12 cells: about 26.4–27.6 V)
Lead-acid boost or equalize, per cell2.35–2.45 V, timed, then back to float
Lead-acid rested open-circuit, full2.10–2.13 V per cell; a 12 V block 12.6–12.8 V
Specific gravity, flooded lead-acid, full1.250–1.280 at 25 °C; some makers use 1.215–1.240; discharged near 1.150; add 0.004 per 6 °C above reference
SG spread across cellswithin 0.020–0.030; one cell further out is the bad cell
NiCd float / boost, per cell1.40–1.45 V / 1.55–1.70 V; nominal 1.2 V
Charger ammeter at floatnear zero: standing DC load plus a trickle
UPS runtimeper maker, commonly 15–60 min at rated load; the display estimate assumes healthy batteries
GMDSS reserve battery1 hour with an emergency generator fitted, 6 hours without

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Charger volts normal; battery voltage collapses with the charger offVoltage per block or cellDead or sulfated bank; open cellFind the bad block; other bank; replace
Charger ammeter high at float and never fallsBank temperature; levelsShorted cell; thermal runaway on VRLA; float set highPer-block voltage; isolate a hot bank
Charger output zero, DC bus lowCharger AC supply, breaker, fusesSupply lost; charger failed; DC fuseRestore — the bank is discharging now
One cell SG 0.030 or more below the restIts level and voltageWeak or shorted cellOne equalize; still low — replace it
Crust on terminals; voltage drop under loadTerminalsAcid mist; loose jointIsolate, clean, retorque, grease
Emergency generator cranks slowly or not at all; bank reads normal at restVoltage during cranking; terminalsHigh-resistance joint; weak bank; coldClean and tighten; other bank; spring starter
UPS ON BATTERY with the board liveUPS input breaker, input volts and HzInput out of tolerance; input fuse; rectifier faultFix the input — it is discharging
UPS "replace battery" alarm, runs fine on AC powerBattery date; self-test logString failed its self-testReplace before you need it
UPS on BYPASS, nobody knows whyEvent logOverload transferred it; inverter fault; left after serviceFind the cause; return to NORMAL
Bank hot, hard gassing, rotten-egg smell, levels droppingCharger mode and voltageBoost stuck on; regulator failed; shorted cellCharger to float or off; ventilate; top up after