Part II · The Equipment · Family 4 · Control It · Stage 1 · Before your first watch

Valves

Valves decide where every fluid goes, how much gets there, and which way it may flow. Most lineup mistakes are a valve in the wrong position or a valve that isn't holding.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
HandwheelClockwise to close, viewed from the wheel
Rising-stem gate or globeStem out = open; stem in = closed
Ball, butterfly, plugHandle in line with the pipe = open; across = closed
Gate or globe "fully open"To the stop, then back ¼–½ turn
Valve glandDry. Weep — take it up; drip — repack
Relief valveSeated, quiet, outlet dry
Reducing valveDownstream steady at set; no creep when flow stops
Stopped standby pumpDoesn't turn backwards
Remote valveIndicator matches mimic and lineup

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Pressure stays on an isolated sectionSection gauge; each boundary valveA valve leaking byAdd a third valve; find the passing one
Remote valve shows open, no flowPump suction gauge; the valveActuator stuck; coupling shearedCycle it; prove with manual override
Handwheel turns, nothing changesIs the stem rising?Wedge off stem; threads stripped; disc pin shearedIsolate elsewhere; open up
Won't close the last turnBody bottomScale, rags, growth on the seatOpen a few turns, re-close; open bonnet
Valve won't moveWhen it was last workedSeized stem; thermal binding; corroded skin valveWork gently; don't force a skin valve
Gland weeping or drippingGland nutsPacking worn or looseTake up a flat; repack if no response
Standby pump turning backwardsIts discharge checkCheck stuck open or seat failedShut its discharge; overhaul the check
Pump won't pull from one tank or wellSuction bonnetsRags; stop-check disc stuck; valve shutOpen bonnets and clear
Relief weeping or liftingPressure vs setOver-pressure; dirt on seat; setting driftedFind cause; lift to clear; bench reset
Reducer outlet rising to supplyFlow at the timeSeat leaking at no flowClean or rebuild seat
Temperature hunting on a three-wayAuto or manual; positionPositioner; tired wax elementHand-control; repair
Fire main won't hold pressureOverboard and hydrant valvesFire pump overboard left cracked after stripping; hydrant leakingClose tight; use a different hydrant