Part II · The Equipment · Family 5 · Power It · Stage 4 · Moving up

Transformers

Transformers step the 440 V bus down to 220 V or 120 V for lighting and small power, isolate shore power and sensitive loads from the ship's system, and scale current and voltage down so meters and relays can read them. With no moving parts, almost everything that goes wrong is heat, moisture, or a loose connection.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Lighting transformer ratio440 → 220 V (230 or 115/120 V on some ships); three-phase, dry type
Ratingtens to a few hundred kVA each; two in parallel or one duty, one standby
Secondary voltage, no load to full loadfalls 2–4 %; taps correct it
Tapson the primary, changed dead; ±2.5 % and ±5 % are common
Insulation classF (155 °C) or H (180 °C); winding rise per nameplate
CoolingAN (natural air through louvers) or AF (fan started by winding temperature)
Humsteady, at twice line frequency; a change of pitch or a rattle is the fault
Phase current balancewithin 10–15 % of each other
Insulation resistance500 V DC on the 440 V side, 250 V on the 220 V side; 1 MΩ floor, healthy reads tens to hundreds of MΩ; trend it
Magnetizing inrush8–12 × full-load current for a few cycles on energizing
CT secondary5 A (or 1 A) at rated primary current
VT secondary110 or 120 V at rated primary voltage
Parallel operationsame ratio, same vector group, same tap; impedance within about 10 %

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Secondary volts low, primary normal, lights dim at peak loadTap position; secondary ampsRegulation under heavy load; tap one step lowShed or rebalance; retap one step, dead, on all parallel units
Secondary volts high, lamps burning outTap; primary voltsTap left high after replacement; generator AVR set highSet tap; see Generators and AVRs
Hotter than usual at the same loadLouvers; fan; room temperatureBlocked ventilation; fan failed; hot ERClear, repair, shift load to the other unit
One phase hotter, one phase amps highLoad split; terminal scanSingle-phase loads unbalanced after a refit; loose terminal on that phaseMove circuits between phases; retorque dead
Hum louder or changed; rattleBus volts and Hz; clamp bolts; panelsOvervoltage; loose core clamps or enclosure panelCorrect volts; tighten dead
Feeder breaker trips the instant it is energizedTrip type on the breakerMagnetizing inrush on an instantaneous setting; genuine shortMegger first; clean and trips again — instantaneous set too low for inrush
220 V ground lamp dim on one phase220 V consumers one at a timeGround on a lighting circuit; winding to coreFind the circuit; megger the transformer if nothing else clears it
Megger down from last readingRoom humidity; dust and salt on windingsMoisture; dirt; oil mistClean, dry out, retest
Feeder ammeter reads zero, motor runningMeter selector; CT shorting linksLinks left in after work; meter or selector deadDo not lift a wire on a live CT loop — isolate first
Voltmeter zero on one phase, bus liveVT secondary fusesFuse blownReplace; check what relays saw
Two parallel units: current flowing at no load, both warmTap positions on eachTap or vector group mismatch — circulating currentMatch taps; confirm vector groups