Tanks, Soundings, and Level Gauges

A tank holds a liquid where you can find it again, breathes as the level changes, and tells you how much is in it. The sounding tape is the only instrument aboard that answers how much directly; everything else is a trend.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Sounding pipe bore32–50 mm
Air pipe height above deck760 mm freeboard deck · 450 mm superstructure deck
Remote gauge (TLI) on an empty storage tank3–7 m³ dead band — record yours
Bunker fill limit85–90 % of capacity, by company rule
Trim correction columns0.5 or 1 m steps, usually to 3–4 m by the stern
Residual fuel volume changeabout 0.06–0.07 % per °C
Steam to heating coils4–8 bar reduced; condensate back through traps
Sludge and oily bilge tank for discharge40–50 °C
Pump-down limit, heated dirty tanks15–25 cm — below that the pump loses suction on sediment
Tank being filledsounded every 15–30 min by tape

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
TLI reads several m³, tape says emptyEmpty-tank recordDead band; trim; sludge at the dip tubeReport the sounding; record the dead band
TLI and local gauge climb fast at bunkeringTank ventFloat stuck; gauze blocked; filling faster than the ventSlow the fill; clear the vent
Sounding up on a tank nobody filledKick for water; make-up feedCoil leak; fill or crossover valve passing; bulkhead leakIsolate the coil; prove valves one at a time
Water at the kick mid-transferSource tankOverflow tank sent unsounded; coil leak; wet bunkerStop transfer and purifier; call the 1st or Chief
Tape hangs up, reads shortPipe on the plan; pipe boreBent pipe; treatment chemical congealed in the pipeUllage; flush with diesel; dose with diesel behind
Tape goes past the reference heightStriking platePlate corroded throughStop using that pipe; report; inspect at entry
Soundings and flow meter disagreeTemperatures; trim; overflow returnsNo temperature correction; returns counted twice; meter driftRecalculate; reconcile with the Chief
Tank holds less than the tableSediment depth at last openingMud or sludge; blocked limber holesNote working capacity; clean at next opening
Transfer pump at full vacuum, strainer cleanVent; valve at its override; tank temperatureVent blocked; valve not open; cold fuelClear vent; prove valve; heat the tank
Small tank overflowedAuto-stop floatFloat stuck; operator left; overflow routed to storageTest the auto-stop; stay with every fill
Two tanks equalizingSuction and crossover lineupTwo suctions on a common lineOne suction at a time; close at the tank
Oil in observation tank or hotwellHeating lineupHoled coil or fuel heater tubeIsolate coils one at a time; blank; pads in the hotwell
Potable tank gauge disagrees with tapeSuction lineup; gauge glass fittingsGauge fault; two suctions openReport soundings; close one suction