The main switchboard joins the generators to the bus and the bus to every feeder, and its breakers and relays decide what gets disconnected when something goes wrong. Reading a trip correctly, resetting it safely, and racking a breaker are Stage 1; relay settings and discrimination are Stage 4 and are marked where they come up.
protection detail: Stage 4
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Bus voltage / frequency | 440–450 V, 60 Hz; limits in Electrical Plant, At a Glance |
| ACB positions | CONNECTED · TEST · DISCONNECTED (some add REMOVED) |
| Closing springs | recharged by motor within seconds of each close; flag shows CHARGED |
| Undervoltage release | opens the breaker between 70 % and 35 % of rated; allows closing at 85 % or more |
| Shunt trip coil | trips anywhere from 70–110 % of control voltage |
| Check-synchronizing window | voltage within 5–10 %, slip under 0.1–0.3 Hz, phase within 10–20° |
| Preferential trip | picks up near 100–110 % of a set's rating; stages a few seconds apart |
| MCCB handle | ON · TRIPPED (mid-position) · OFF/RESET |
| Insulation monitor alarm | per maker and class; commonly tens to low hundreds of kΩ |
| Terminal hot spot | 4 °C or more above matching joints at the same load — investigate; over 15 °C, repair now |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| ACB won't close, no trip showing | Spring flag; position; incoming voltage | Springs not charged; not fully CONNECTED; UVR not energized; mechanical reset not pushed; interlock; control fuse | Work through in that order |
| ACB closes and opens at once | Relay and trip unit display | Fault still present; UVR not picked up; trip signal standing | Read the flag; clear the cause |
| Generator ACB won't close on auto-sync, closes by hand | Incoming Hz and volts vs bus | Sync window not reached; auto-synchronizer governor trim fault | Bring the set slightly fast by hand, back to auto |
| Generator ACB tripped, relay flag shown | The flag | See protection table | Record, fix cause, reset relay, reset breaker, close once |
| ACB opened, no relay flag | What else happened at that moment | UVR drop on a voltage dip or control supply; shunt trip from an engine shutdown, emergency stop, or preferential trip | Find the signal source before re-closing |
| Feeder MCCB handle at mid-position | The load | Overload; motor fault; short | OFF, then ON, once; trips again — megger before more |
| Feeder and generator breaker tripped on one fault | Which feeder | Discrimination failure (Stage 4) | Isolate the feeder; restore the bus; report |
| Non-essential groups dead after a set tripped | Preferential trip indicators | Preferential trip operated | Restore groups one at a time, kW meter in view |
| Racking handle won't insert or won't turn | Breaker ON/OFF; padlocks; position lock | Breaker closed; padlock or key interlock; position lever not released | Open breaker, release interlock — never force it |
| Insulation monitor reads infinite or off-scale high | Monitor power and selection; test button | Monitor switched out with bus-tie; monitor dead; disconnected | Confirm one monitor in service per connected system |
| Ground alarm the moment shore power closes | Shore supply type | Grounded shore neutral, no isolation transformer; ground in shore cable | Log it if normal for that berth; megger the cable if not |
| Warm panel door, smell, discolored terminal | Feeder amps; thermal scan | Loose or oxidized joint; overloaded feeder | Reduce load; plan a dead-board retorque |
| Emergency board dead, emergency generator running | Its voltage; interconnector position | Voltage not built; interconnector still closed; ACB not reset after test | Close manually at nominal V and Hz |