Part I · The Plants

Steam Plant

The steam plant heats the heavy fuel so the engines can burn it, and heats the tanks, purifiers, jacket water, accommodation, and galley. At sea the exhaust gas boiler (EGB) makes the steam for free; in port and at low load the oil-fired auxiliary boiler takes over.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Steam pressure, heating plant6–9 bar (some ships up to 16)
Burner fuel pressure, pressure jet15–25 bar
HFO temperature at burner115–130 °C, by grade
Exhaust temperature before EGB250–350 °C
Exhaust temperature after EGB180–250 °C; not below 160
Hotwell temperature80–90 °C
Boiler water pH10.5–11.5
P-alkalinity100–300 ppm as CaCO₃
Phosphate (phosphate programs)15–50 ppm
Chlorides, boiler water< 200–300 ppm
Chlorides, condensate and makeup< 10 ppm
Hardness0 (< 2 ppm)
Hydrazine · or sulfite0.1–0.2 ppm · 20–50 ppm
Trap outlet below steam temperature5–20 °C

The tour

The plant, stop by stop, as the book walks it.

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Drum level swingingBoth glasses; TDS; observation tankRegulator hunting; foaming from TDS, oil, or treatment solidsSurface blowdown; check for oil; regulator to manual
Level falling under steady load, feed runningBlowdown valves; feed check; hotwellBlowdown passing; tube leak; pump not deliveringShut blowdown; standby pump; look for steam at the stack
Low water alarmGlass; feed pump; hotwellPump vapor-bound; regulator failed closed; blowdown openBurner off; feed by hand if the glass shows water; if not, stay off until cool
Standby feed pump turning backwardsIts discharge checkCheck valve failedReplace the check
Ignition transformer keeps failingAuto sequence; recently replaced sensorsRunning in manual; sensor not configuredFix the input; back to auto
EGB outlet temperature and ΔP risingSoot blowers; circulating pumpFouled tubes; soot fire if rising with engine stoppedSoot blow; fire — Stop 4
Water hammer in a lineDrains; traps on that lineCold line opened fast; trap stuck closedClose, drain, warm through; change trap
Oil on the observation tankFO and purifier heaters; tank coilsHeater tube or coil leakCondensate to bilge; isolate consumers one at a time
Makeup use up sharplyDump condenser drains; traps; heated tanksCondenser bypassed; trap blowing; coil leakCondenser in service; trap survey; sound tanks for water
Hotwell rising with makeup shutDump condenser; drain coolersCooling water leaking into condensateTest condensate for inhibitor; pressure test
Chlorides and conductivity jump after a top-upWhat went in; makeup floatPotable used as makeup; float failedBlow down; distillate only; repair float
Chlorides and hardness rising togetherMakeup water; drain coolerSeawater inIsolate; blow down; retest

Scenarios

Work out what you’d do, then open it.

inhibitor disappearing, boiler conductivity rising

For months, nitrite in the cooling water won't stay up despite hard dosing. No visible leak; bacteria test negative. Boiler conductivity rises with each cooling water dose, and extra bottom blows don't help. Now the hotwell overflows daily and the boiler primes and trips on high water. What is it?

Two trends in two plants are one fault: something cooled by treated water is leaking into the condensate. On most plants that is the LT-cooled dump condenser or a drain cooler. Isolate it, pressure test the cooling side, and test the condensate for the inhibitor. Once it is replaced, both chemistries hold.

boiler starving, water in the feed tank

The hotwell is low and the boiler short of feed, but the distilled feed tank is full. The last watch topped up from potable and chlorides spiked. What should have been checked first?

Either the makeup float valve isn't passing — stuck or broken, a recurring fault — or the hotwell ran hot and the feed pumps are vapor-bound. Vent the pump casing first and watch the drum level respond. Then the float: open the makeup bypass from the distillate tank, not the potable valve.

oil on the observation tank

A sheen at 0400. FO and purifier heaters on steam, tank coils open. What now?

Divert condensate to the bilge tank. Skim the hotwell, pads in the hotwell and observation tank, surface-blow the drum. Isolate heaters one at a time, five minutes each, watching the observation tank; then the coils. The one that stops the sheen gets its steam side blanked until a new bundle arrives. Then find out why the oil detector didn't alarm. The condensate to the bilge tank goes in the ORB.

steam lost

The aux boiler trips on low-low water in port with the EGB cold. An hour before it can be refilled and fired. What stops, and in what order?

Nothing in the first minutes — heaters and coils hold heat. Within half an hour fuel at the generator heaters cools past what the controller can hold; change the generators to MDO now. Over the next hours bunker tanks cool and the transfer pump labors, purifiers stop separating, and the main engine's jacket water cools. Refilling a drained boiler takes many metric tons, so check the feed tank — and the water-mist system if it shares that suction.

Dependencies

Needs
  • Electrical — fan, fuel pump, feed pumps, circulating pump, controls
  • Fuel plant — boiler fuel at atomizing temperature on HFO
  • Freshwater plant — distilled makeup
  • LT or seawater cooling — dump condenser and drain coolers
  • Compressed air — damper and fuel valve actuators
  • Main engine exhaust — the EGB
Feeds
  • Fuel plant — FO heaters, purifier heaters, tank coils; through them every engine on HFO
  • Lube oil plant — purifier heaters, tank heating
  • Main engine jacket water heating in port
  • Sludge, oily bilge, and waste oil heating
  • Accommodation heating, galley, calorifier