Part I · The Plants

Seawater and Central Cooling

Seawater carries the ship's waste heat overboard through two central coolers; two closed freshwater circuits carry that heat from the machinery to the coolers. The low-temperature (LT) circuit cools everything with a cooler on it; the high-temperature (HT) circuit cools the main engine and feeds the freshwater generator (FWG).

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
SW inletambient, up to 32 °C design
SW outlet from central coolerinlet + 5–10 °C
SW pump discharge2–3 bar
Strainer ΔP — clean / change over< 0.1 / 0.3 bar
LT supply to consumers35–40 °C (set point ~36 °C)
Approach (LT out − SW in), clean cooler3–6 °C
HT outlet from main engine80–90 °C
HT ΔT across engine, full load5–12 °C
HT and LT pump differential2.5–4 bar
HT held by preheater, engine stopped50–60 °C minimum
pH8.3–10
Nitrite (as NO₂⁻)1,000–2,400 ppm
Chloride< 50 ppm
Hardness< 10 ppm CaCO₃

The tour

The plant, stop by stop, as the book walks it.

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
SW suction flickering, pumps rattling, amps lowStrainer ΔP; which chest is openGrid blocked; strainer loaded; chest drawing airChange over chest or strainer; blow the chest; vent
LT supply creeping up over days, SW temp steadyCooler approach and SW ΔTSW-side fouling; MGPS off; three-way valve driftConfirm by approach; clean cooler; check MGPS
Charge air temperature at alarm, LT normalCooler ΔP; isolation valvesAir or LT side fouled; dirty turbo compressor; valves leaking byBackflush LT side; wash turbo; then ask for less load
ECR AC or refrigeration tripping on head pressureLT cooler strainerStrainer fouling; LT supply warmSwap coolers; reset; clean the offline strainer now
HT outlet high, LT normalThree-way valve positionValve on bypass; HT cooler scaled; air lockHand-control the valve; vent; check HT cooler ΔT
HT outlet climbing while securing the FWGFWG HT valves and bypassHT valves closed too fast or with bypass throttledOpen the bypass; reopen HT valves; go a notch a minute
HT outlet low under loadThree-way valve position; FWGValve stuck to cooler; FWG at low load; sensorHand-control; reduce or stop FWG
Expansion tank fallingAdditions per day; FWG running?FWG plate; head gasket or liner; coolerStop the FWG as the first test
Expansion tank rising, or bubblingChlorides; which cylinder outlet is highSW through a cooler; gas from a head or linerTest chlorides; isolate coolers; inspect the unit
One head tank rising, the other fallingCrossover; HT coolerCross-leak at the HT cooler or charge air coolerOpen the crossover; find and fix the leak
Chlorides rising, nitrite fallingDistillate tank chloridesCentral cooler; FWG; SW-cooled aux coolerIsolate and pressure-test; dose after the fix
Nitrite won't hold, chlorides steady, bacteria cleanBoiler water conductivityCondenser cooled by treated water leaking into condensateIsolate that condenser; test both systems together
Oil on the expansion tankWhich machines are runningLO cooler leaking into LTRun one machine at a time; isolate that cooler
Engine or standby set weeping water after a stopIts HT temperaturePreheater off; cooling inlet valve stuck openRestore preheat; exercise the valve

Scenarios

Work out what you’d do, then open it.

charge air climbing on a hot passage

Full load, warm sea. Charge air temperature is at 67 °C against an alarm of 65 and creeping up. LT supply is at set point. What can you do from the engine room before asking the bridge to slow down?

LT at set point means the central coolers are coping; the problem is at the charge air cooler. Backflush its LT side, water-wash the turbo compressor, check its air-side ΔP, and confirm the second central cooler is on line. Still climbing: ask the bridge for less pitch or speed before it becomes a slowdown. If it recurs every hot passage after every repair, check the isolation valves and whether LT heat load was added after the coolers were sized.

oil in the expansion tank

An oil sheen comes and goes in a shared HT/LT expansion tank, heaviest after a port stay. One generator's LO sample shows over 5 % water, though its log has always read under 1 %. What's happening?

A generator LO cooler is leaking both ways — oil into the water when running, water into the oil when stopped. The log read low because samples came from the dipstick tube, not the sample point. Run one machine at a time and watch which one brings the oil back. Replace the cooler — the purifier won't keep up with an active leak — then renew the sump oil and filters and skim the tank.

disappearing inhibitor

For months, nitrite won't stay up despite hard dosing. No visible leak, chlorides steady, bacteria test negative. Meanwhile boiler water conductivity rises after each cooling water dose, and the hotwell starts overflowing. What links them?

A condenser cooled by treated LT water — a steam dump condenser — is leaking cooling water into the condensate. Each dose goes to the boiler, where the solids make it prime and trip on high water level faster than blowdown can clear them. Isolate the condenser; when nitrite holds and conductivity stops climbing, you've found it. Read the two systems' trends together.

sea chest blocked under way

Coastal passage, 0200. SW suction falling, both SW pumps rattling, LT supply starting to rise. What stops, in what order, and what do you do first?

Change over to the other sea chest now and vent the strainers. If suction comes back, the rest is cleanup. If not, you have minutes. Charge air and exhaust temperatures rise first; then LO temperature; HT outlet climbs with its valve at full cooling; ECR AC and refrigeration trip on head pressure; compressors trip; the main engine alarms on HT and slows down. Tell the bridge before the slowdown and ask for reduced load while you blow the chest. If you must choose, keep the generators cool — losing the switchboard loses every pump.

Dependencies

Needs
  • Electrical — SW, LT, and HT pumps, MGPS, valve actuators
  • Control air — pneumatic three-way valves
  • Distilled water from the FWG — makeup
  • Steam or electricity — preheater and jacket water heater
  • Treatment chemicals and a test kit
Feeds
  • Main engine — jackets, charge air cooler, LO cooler
  • Generators — jackets and coolers
  • Air compressors
  • Refrigeration and AC condensers, including the ECR
  • Hydraulic power units
  • Freshwater generator — heat source and condenser cooling
  • Steam dump condenser where LT-cooled
  • Stern tube and bearing coolers where LT-cooled