Seawater carries the ship's waste heat overboard through two central coolers; two closed freshwater circuits carry that heat from the machinery to the coolers. The low-temperature (LT) circuit cools everything with a cooler on it; the high-temperature (HT) circuit cools the main engine and feeds the freshwater generator (FWG).
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| SW inlet | ambient, up to 32 °C design |
| SW outlet from central cooler | inlet + 5–10 °C |
| SW pump discharge | 2–3 bar |
| Strainer ΔP — clean / change over | < 0.1 / 0.3 bar |
| LT supply to consumers | 35–40 °C (set point ~36 °C) |
| Approach (LT out − SW in), clean cooler | 3–6 °C |
| HT outlet from main engine | 80–90 °C |
| HT ΔT across engine, full load | 5–12 °C |
| HT and LT pump differential | 2.5–4 bar |
| HT held by preheater, engine stopped | 50–60 °C minimum |
| pH | 8.3–10 |
| Nitrite (as NO₂⁻) | 1,000–2,400 ppm |
| Chloride | < 50 ppm |
| Hardness | < 10 ppm CaCO₃ |
The plant, stop by stop, as the book walks it.
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| SW suction flickering, pumps rattling, amps low | Strainer ΔP; which chest is open | Grid blocked; strainer loaded; chest drawing air | Change over chest or strainer; blow the chest; vent |
| LT supply creeping up over days, SW temp steady | Cooler approach and SW ΔT | SW-side fouling; MGPS off; three-way valve drift | Confirm by approach; clean cooler; check MGPS |
| Charge air temperature at alarm, LT normal | Cooler ΔP; isolation valves | Air or LT side fouled; dirty turbo compressor; valves leaking by | Backflush LT side; wash turbo; then ask for less load |
| ECR AC or refrigeration tripping on head pressure | LT cooler strainer | Strainer fouling; LT supply warm | Swap coolers; reset; clean the offline strainer now |
| HT outlet high, LT normal | Three-way valve position | Valve on bypass; HT cooler scaled; air lock | Hand-control the valve; vent; check HT cooler ΔT |
| HT outlet climbing while securing the FWG | FWG HT valves and bypass | HT valves closed too fast or with bypass throttled | Open the bypass; reopen HT valves; go a notch a minute |
| HT outlet low under load | Three-way valve position; FWG | Valve stuck to cooler; FWG at low load; sensor | Hand-control; reduce or stop FWG |
| Expansion tank falling | Additions per day; FWG running? | FWG plate; head gasket or liner; cooler | Stop the FWG as the first test |
| Expansion tank rising, or bubbling | Chlorides; which cylinder outlet is high | SW through a cooler; gas from a head or liner | Test chlorides; isolate coolers; inspect the unit |
| One head tank rising, the other falling | Crossover; HT cooler | Cross-leak at the HT cooler or charge air cooler | Open the crossover; find and fix the leak |
| Chlorides rising, nitrite falling | Distillate tank chlorides | Central cooler; FWG; SW-cooled aux cooler | Isolate and pressure-test; dose after the fix |
| Nitrite won't hold, chlorides steady, bacteria clean | Boiler water conductivity | Condenser cooled by treated water leaking into condensate | Isolate that condenser; test both systems together |
| Oil on the expansion tank | Which machines are running | LO cooler leaking into LT | Run one machine at a time; isolate that cooler |
| Engine or standby set weeping water after a stop | Its HT temperature | Preheater off; cooling inlet valve stuck open | Restore preheat; exercise the valve |
Work out what you’d do, then open it.
Full load, warm sea. Charge air temperature is at 67 °C against an alarm of 65 and creeping up. LT supply is at set point. What can you do from the engine room before asking the bridge to slow down?
LT at set point means the central coolers are coping; the problem is at the charge air cooler. Backflush its LT side, water-wash the turbo compressor, check its air-side ΔP, and confirm the second central cooler is on line. Still climbing: ask the bridge for less pitch or speed before it becomes a slowdown. If it recurs every hot passage after every repair, check the isolation valves and whether LT heat load was added after the coolers were sized.
An oil sheen comes and goes in a shared HT/LT expansion tank, heaviest after a port stay. One generator's LO sample shows over 5 % water, though its log has always read under 1 %. What's happening?
A generator LO cooler is leaking both ways — oil into the water when running, water into the oil when stopped. The log read low because samples came from the dipstick tube, not the sample point. Run one machine at a time and watch which one brings the oil back. Replace the cooler — the purifier won't keep up with an active leak — then renew the sump oil and filters and skim the tank.
For months, nitrite won't stay up despite hard dosing. No visible leak, chlorides steady, bacteria test negative. Meanwhile boiler water conductivity rises after each cooling water dose, and the hotwell starts overflowing. What links them?
A condenser cooled by treated LT water — a steam dump condenser — is leaking cooling water into the condensate. Each dose goes to the boiler, where the solids make it prime and trip on high water level faster than blowdown can clear them. Isolate the condenser; when nitrite holds and conductivity stops climbing, you've found it. Read the two systems' trends together.
Coastal passage, 0200. SW suction falling, both SW pumps rattling, LT supply starting to rise. What stops, in what order, and what do you do first?
Change over to the other sea chest now and vent the strainers. If suction comes back, the rest is cleanup. If not, you have minutes. Charge air and exhaust temperatures rise first; then LO temperature; HT outlet climbs with its valve at full cooling; ECR AC and refrigeration trip on head pressure; compressors trip; the main engine alarms on HT and slows down. Tell the bridge before the slowdown and ask for reduced load while you blow the chest. If you must choose, keep the generators cool — losing the switchboard loses every pump.