A refrigeration compressor pulls low-pressure vapor off the evaporators and pushes it into the condenser at a pressure where cooling water can turn it back into liquid. It is the only part of the circuit that moves, and most of what destroys it arrives through the suction line: liquid, oil that didn't come back, or not enough gas.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Net oil pressure, recip with oil pump (oil gauge minus suction) | 1.5–4 bar |
| Sump level, recip, running | on the maker's mark, ¼–¾ glass; steady |
| Crankcase, stopped, heater on | warm to the hand |
| Discharge line at the compressor | 60–90 °C; trip 110–120 °C |
| Discharge superheat (discharge temp − condensing temp) | 20–50 K; low or falling means liquid is getting in |
| Compression ratio, absolute pressures | AC 2.5–4 · cold rooms 3.5–5 · freezers 7–12 |
| Starts per hour | 6–10 maximum; minimum run 3–5 min |
| Amps | 60–95 % of nameplate steady; higher only on pulldown |
| Screw slide valve range | 10 or 25 % to 100 % |
| Crankcase heater before a start after a long stop | 6 h minimum |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Oil pressure trip at or soon after start | Sump foam; crankcase warm? | Flooded start — heater off or not on long enough; low oil; worn pump; blocked strainer; pump reversed after motor work on an open machine | Heater on and wait; read the true level once the foam clears |
| Sump falling over days, no leak found | Load profile | Oil logged at low load; separator oil return blocked; shaft seal | Run loaded; clear the return; leak test the seal |
| Sump rising and foaming, crankcase cold | Frost on the suction line; coil fans | Floodback | Fix it at the evaporator (Refrigeration Components) |
| Knock that stays | Heads by hand | Broken valve plate, rod, or bearing | Stop; open the head |
| Trips on discharge temperature | Suction superheat at the compressor; ratio | Starved coil or low charge; very low suction; leaking discharge valve; head fan off | Fix superheat; valve plate; cooling |
| Suction high, discharge low, amps low, box won't pull down | Heads by hand; unloader steps | Leaking valve plate or head gasket; unloader stuck unloaded; worn rings | Find the odd head; valve plate; unloader |
| Amps high, pressures normal | Amps on each phase | Single-phasing; low voltage; bearing; misalignment; belts too tight | Electrical first, then mechanical |
| Scroll loud, no pressure split, trips after electrical work | Phase sequence | Reverse rotation | Swap two phases at the starter |
| Screw discharge temperature climbing, capacity falling | Oil filter ΔP; oil temperature | Filter blocking; oil cooler fouled; liquid injection not opening; low charge | Filter; cooler; injection valve |
| Screw parked at minimum slide, separator oil falling | Load; slide solenoids | Oil logging at low gas velocity; slide stuck | Let it cycle off; free the slide |
| Centrifugal surging | Head; guide vanes | Low load with high head; condenser fouled; air; vanes not closing | Cut the head at the condenser; purge; vendor |
| Won't start, no trip showing | Anti-recycle timer; LP; solenoid | Timer running; low side below cut-in; solenoid not energized | Wait; read the panel |