Part II · The Equipment · Family 1 · Move It · Stage 2 · First month

Refrigeration Compressors

A refrigeration compressor pulls low-pressure vapor off the evaporators and pushes it into the condenser at a pressure where cooling water can turn it back into liquid. It is the only part of the circuit that moves, and most of what destroys it arrives through the suction line: liquid, oil that didn't come back, or not enough gas.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Net oil pressure, recip with oil pump (oil gauge minus suction)1.5–4 bar
Sump level, recip, runningon the maker's mark, ¼–¾ glass; steady
Crankcase, stopped, heater onwarm to the hand
Discharge line at the compressor60–90 °C; trip 110–120 °C
Discharge superheat (discharge temp − condensing temp)20–50 K; low or falling means liquid is getting in
Compression ratio, absolute pressuresAC 2.5–4 · cold rooms 3.5–5 · freezers 7–12
Starts per hour6–10 maximum; minimum run 3–5 min
Amps60–95 % of nameplate steady; higher only on pulldown
Screw slide valve range10 or 25 % to 100 %
Crankcase heater before a start after a long stop6 h minimum

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Oil pressure trip at or soon after startSump foam; crankcase warm?Flooded start — heater off or not on long enough; low oil; worn pump; blocked strainer; pump reversed after motor work on an open machineHeater on and wait; read the true level once the foam clears
Sump falling over days, no leak foundLoad profileOil logged at low load; separator oil return blocked; shaft sealRun loaded; clear the return; leak test the seal
Sump rising and foaming, crankcase coldFrost on the suction line; coil fansFloodbackFix it at the evaporator (Refrigeration Components)
Knock that staysHeads by handBroken valve plate, rod, or bearingStop; open the head
Trips on discharge temperatureSuction superheat at the compressor; ratioStarved coil or low charge; very low suction; leaking discharge valve; head fan offFix superheat; valve plate; cooling
Suction high, discharge low, amps low, box won't pull downHeads by hand; unloader stepsLeaking valve plate or head gasket; unloader stuck unloaded; worn ringsFind the odd head; valve plate; unloader
Amps high, pressures normalAmps on each phaseSingle-phasing; low voltage; bearing; misalignment; belts too tightElectrical first, then mechanical
Scroll loud, no pressure split, trips after electrical workPhase sequenceReverse rotationSwap two phases at the starter
Screw discharge temperature climbing, capacity fallingOil filter ΔP; oil temperatureFilter blocking; oil cooler fouled; liquid injection not opening; low chargeFilter; cooler; injection valve
Screw parked at minimum slide, separator oil fallingLoad; slide solenoidsOil logging at low gas velocity; slide stuckLet it cycle off; free the slide
Centrifugal surgingHead; guide vanesLow load with high head; condenser fouled; air; vanes not closingCut the head at the condenser; purge; vendor
Won't start, no trip showingAnti-recycle timer; LP; solenoidTimer running; low side below cut-in; solenoid not energizedWait; read the panel

Draft: this page is drawn from the book manuscript and is still being checked.