A heat exchanger moves heat from one fluid to another through a wall that keeps them apart. You judge every one by four temperatures and two pressure drops; most faults are fouling, low flow, or a leak through that wall.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Central cooler approach (LT out − SW in), clean | 3–6 °C |
| SW temperature rise across a central cooler | 5–10 °C |
| ΔP per side, plate exchanger | 0.3–1.0 bar |
| ΔP per side, shell-and-tube | 0.2–0.7 bar |
| Clean-and-inspect trigger | approach 3–4 °C above clean baseline at the same load |
| LO cooler outlet (engine inlet) | engine maker's figure — roughly 40–50 °C slow-speed, 55–65 °C medium-speed |
| Calorifier outlet / loop return | ≥ 60 °C / > 50 °C |
| Plate pack tightening dimension | between the maker's min and max — on the plate |
| Sacrificial anode renewal | ~50 % consumed, or per maker |
| Tubes plugged before retubing | maker's or class limit, commonly ~10 % |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Hot-side outlet rising, same load | Approach; cooling-side ΔT | Fouling; low cooling flow; control valve | Work the pattern table; backflush or clean; fix the flow |
| Cooling-side ΔP rising, temperatures fine | Inlet ports or tube ends | Debris lodging; fouling starting | Backflush; schedule cleaning |
| Charge air temperature high, LT at set point | LT in/out of the charge air cooler; air-side ΔP | LT side fouled; air side oily; isolation valves leaking by | Backflush LT side; chemical-wash air side; wash turbo compressor |
| Oil in the cooling water expansion tank | Which machines are running | LO or fuel cooler leaking | Run one machine at a time and watch the tank |
| Water in an engine sump | Sump drain; water test from a live line | LO cooler leaking water in while stopped; jacket leak | Isolate cooler; pressure test; don't try to purify it out |
| Cooling water inhibitor won't hold, no visible leak | Condensate chemistry; boiler conductivity trend | LT-cooled dump condenser or drain cooler leaking into condensate | Isolate and pressure test the condenser |
| Oil in the hotwell | Each steam heater's drain | Heater tube or coil holed | Isolate heaters one at a time; blank the steam side of the leaker |
| Chlorides rising in freshwater circuit | Expansion tank level; which cooler | Seawater through a plate or tube | Isolate coolers one at a time; pressure test |
| Plate pack leaking at the edge | Where on the pack; vent holes | Gasket aged or displaced; pack loose; port gasket failed | Tighten within limits if allowed; regasket |
| Plate pack leaks after reassembly | Plate order and gaskets | Plate hung wrong way; wrong gasket; pack not parallel | Strip and check pattern and part numbers |
| Calorifier outlet low | Element amps; thermostat; steam supply | Element burnt out; thermostat set low; auto control failed | Check each element; set ≥ 60 °C; manual control on the round sheet |
| Anode untouched at inspection | Anode connection | Painted, scaled, or not electrically bonded | Clean contact; check continuity; renew |
| Cooler can't keep up in warm water after every repair | Heat load history | Load added after build; undersized | Second cooler on line; raise with the 1st |
Draft: this page is drawn from the book manuscript and is still being checked.