Heat Exchangers

A heat exchanger moves heat from one fluid to another through a wall that keeps them apart. You judge every one by four temperatures and two pressure drops; most faults are fouling, low flow, or a leak through that wall.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Central cooler approach (LT out − SW in), clean3–6 °C
SW temperature rise across a central cooler5–10 °C
ΔP per side, plate exchanger0.3–1.0 bar
ΔP per side, shell-and-tube0.2–0.7 bar
Clean-and-inspect triggerapproach 3–4 °C above clean baseline at the same load
LO cooler outlet (engine inlet)engine maker's figure — roughly 40–50 °C slow-speed, 55–65 °C medium-speed
Calorifier outlet / loop return≥ 60 °C / > 50 °C
Plate pack tightening dimensionbetween the maker's min and max — on the plate
Sacrificial anode renewal~50 % consumed, or per maker
Tubes plugged before retubingmaker's or class limit, commonly ~10 %

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Hot-side outlet rising, same loadApproach; cooling-side ΔTFouling; low cooling flow; control valveWork the pattern table; backflush or clean; fix the flow
Cooling-side ΔP rising, temperatures fineInlet ports or tube endsDebris lodging; fouling startingBackflush; schedule cleaning
Charge air temperature high, LT at set pointLT in/out of the charge air cooler; air-side ΔPLT side fouled; air side oily; isolation valves leaking byBackflush LT side; chemical-wash air side; wash turbo compressor
Oil in the cooling water expansion tankWhich machines are runningLO or fuel cooler leakingRun one machine at a time and watch the tank
Water in an engine sumpSump drain; water test from a live lineLO cooler leaking water in while stopped; jacket leakIsolate cooler; pressure test; don't try to purify it out
Cooling water inhibitor won't hold, no visible leakCondensate chemistry; boiler conductivity trendLT-cooled dump condenser or drain cooler leaking into condensateIsolate and pressure test the condenser
Oil in the hotwellEach steam heater's drainHeater tube or coil holedIsolate heaters one at a time; blank the steam side of the leaker
Chlorides rising in freshwater circuitExpansion tank level; which coolerSeawater through a plate or tubeIsolate coolers one at a time; pressure test
Plate pack leaking at the edgeWhere on the pack; vent holesGasket aged or displaced; pack loose; port gasket failedTighten within limits if allowed; regasket
Plate pack leaks after reassemblyPlate order and gasketsPlate hung wrong way; wrong gasket; pack not parallelStrip and check pattern and part numbers
Calorifier outlet lowElement amps; thermostat; steam supplyElement burnt out; thermostat set low; auto control failedCheck each element; set ≥ 60 °C; manual control on the round sheet
Anode untouched at inspectionAnode connectionPainted, scaled, or not electrically bondedClean contact; check continuity; renew
Cooler can't keep up in warm water after every repairHeat load historyLoad added after build; undersizedSecond cooler on line; raise with the engineer in charge