The generator turns the diesel's shaft into three-phase power; the automatic voltage regulator (AVR) holds its voltage by controlling the field. The diesel decides kW and frequency — see Auxiliary Engines. This chapter is the alternator, its excitation, and how sets share load on the bus.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Rating | kVA at 0.8 PF lagging; kW rating = 0.8 × kVA |
| Steady-state voltage | within ±2.5 % of setpoint, no load to full load |
| Voltage dip on a large motor start | 10–15 %, back within ±3 % in about 1.5 s |
| Speed droop (governor) | 3–5 % no load to full load, equal on every set |
| Reactive droop (AVR) | 2–5 % at rated current, equal on every set |
| kW sharing in parallel | within 10–15 % of the largest set's rating |
| kVAr sharing in parallel | within 10 % of the largest set's rating |
| Stator winding temperature | 60–110 °C at load; alarm per maker, often 120–140 °C (Class F insulation) |
| Sleeve bearing temperature | 60–85 °C; alarm about 90–95 °C |
| Insulation resistance, 500 V megger | 1 MΩ floor; healthy tens to hundreds of MΩ; polarization index 2 or more |
| Space heater | on when stopped, off when running |
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Set at speed, voltage a few volts or zero | Hz; AVR fuses and supply; excitation switch | Residual magnetism lost; AVR failed; exciter field open; diode bridge shorted | Fuses and wiring, then flash the field per maker; test diodes |
| Over-voltage, or over-voltage trip, set alone | Sensing fuses and wiring | Sensing lost — AVR sees zero and goes full on; AVR failed; setpoint run up | Standby set on; replace fuse or AVR; run it only in parallel until proven |
| Voltage swings alone at load, steady in parallel | When the AVR was changed | Replacement AVR gain and stability not set up; loose sensing wire | Run only in parallel; set up per maker with someone in the ECR |
| Voltage sags with load, normal at no load | Hz first; AVR output | Engine slowing — under-frequency roll-off; open diode; AVR at its ceiling; droop set too high | Fix the speed first; trend excitation; test diodes |
| kVAr or PF unequal at equal kW | AVR setpoints; droop settings | Setpoints differ; droop pots differ; sensing or CT fault on one set | Trim AVR raise/lower until PFs match; set droop equal |
| kVAr sharing goes wrong when a set is added or removed | Which set changed | Cross-current loop not shorted or not opened by the breaker auxiliary contact; CT reversed | Check the auxiliary contact and CT wiring — engineer job |
| kW split uneven, worse on big load changes | Governor modes and droop | Droop differs; one isochronous, one droop, no load-share link | Trim governors; set equal droop (see Starting, Reversing, Governors, and Control) |
| Breaker closes, set won't take kW | Governor raise; mode; fuel limit | Governor motor or raise signal dead; load limit set low; auto-sync trim fault | Raise by hand; bring it slightly fast and back to auto |
| PF leading on one set, its amps rising, bus volts falling | That set's kVAr meter | Excitation lost — AVR failed low, diode short, exciter open | Open that set's breaker if AVR raise does nothing |
| Winding temperature high at normal load | Phase amps; kVAr; air filter | Blocked filter or louvre; high kVAr; hot engine room; unbalanced phases | Clean filter; even kVAr; balance loads |
| One RTD high or open, the others normal, amps balanced | RTD reading against its spare | RTD or its wiring, junction box | Switch to the spare element; fix wiring |
| Bearing temperature rising | Oil flow sight glass; oil level | Lube oil supply lost; oil ring stuck; shaft current through a failed insulated bearing; misalignment | Unload and stop if rising; restore oil before restart |
| Insulation resistance down on a stopped set | Space heater actually warm; what got wet | Heater failed; water ingress or spray; oil and carbon dust on windings | Heater on, dry out, clean; megger again before starting |
| Space heater on while running, or off while stopped | Breaker or running-signal auxiliary contact | Contact or heater contactor stuck; heater element open | Fix the interlock; clamp the heater current |