Part II · The Equipment · Family 5 · Power It · Stage 1 · Before your first watch

Generators and AVRs

The generator turns the diesel's shaft into three-phase power; the automatic voltage regulator (AVR) holds its voltage by controlling the field. The diesel decides kW and frequency — see Auxiliary Engines. This chapter is the alternator, its excitation, and how sets share load on the bus.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

LessonSynchronizing and Load SharingPut No. 2 generator on the board: match voltage and frequency, close just before 12 on the synchroscope, share the kW with the governors and the kVAR with the AVRs, fix a backward droop CT, and sort six sets that won’t share.LessonProtective Relays: Read the FlagWhat each of the five generator relays watches; a reverse power trip after a slow close; overcurrent that rides through a motor start; the AVR’s relays against the governor’s; differential and its zone; a multifunction relay’s event log; and six trips to sort.LessonThe Synchronous Machine: Two Sets of RulesThe same governor and AVR knobs on a set alone and on a set paralleled. The helper who raised the voltage, the set that motored, and six which-rules calls.LessonThe Frequency Meter Test: Which Loop Is SickOn any generator complaint, look at the frequency meter first. Steady: the AVR side. Swinging or wrong: the engine side. Five complaints, each half walked, and what changes when two sets are paralleled.LessonReading the Switchboard Like a StoryFive meters on each generator panel and the stories they tell: equal kW with unequal amps, unequal kW at the right frequency, a plant near its limit, poor power factor, low volts on every set.LessonShaft Generators: The Engine Doesn’t Care About 60 HzA sister ship with a shaft generator: slow the engine and watch the converter hold 60 Hz, set the condenser’s AVR, short a reefer feeder, then change over to the diesels before the pilot.LessonkW, kVAR, kVA and Power FactorThe meter-in-hand theory under the generator panel: two plates on DG1, SWP1’s triangle from a clamp and a voltmeter, a motor running light, a set at its ammeter limit with kW to spare, two sets not sharing kVAR.LessonThe Alternator in One Line: Two Loops, Three Machines and a BoxDG3 opened up: the power path from the PMG to the bus, the AVR’s loop working on a load step, the maker’s AVR sheet read part by part, a day-one walk round, and why you never megger through the AVR.LessonPlant Tour: The Electrical PlantWalk Hawsepiper’s electrical plant stop by stop on one drawing of the engine room and the accommodation above it, from the emergency generator to the shore connection: what to look at, what normal reads, a call at each stop; then six sets of readings.Simulator · free playParallel the GeneratorsBring a ship's second diesel generator onto the board: match voltage, watch the synchroscope, close the breaker and share the load.Simulator · free playSwitchboard MeterskW, kVAR, kVA, amps and power factor on the generator panel: build the load and watch the power triangle, then read two paralleled generators and fix uneven kW and kVAR sharing.Simulator · free playBrushless AlternatorFollow a brushless alternator's excitation chain from PMG to main field, test the rotating diodes with a meter, and diagnose six excitation faults.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
RatingkVA at 0.8 PF lagging; kW rating = 0.8 × kVA
Steady-state voltagewithin ±2.5 % of setpoint, no load to full load
Voltage dip on a large motor start10–15 %, back within ±3 % in about 1.5 s
Speed droop (governor)3–5 % no load to full load, equal on every set
Reactive droop (AVR)2–5 % at rated current, equal on every set
kW sharing in parallelwithin 10–15 % of the largest set's rating
kVAr sharing in parallelwithin 10 % of the largest set's rating
Stator winding temperature60–110 °C at load; alarm per maker, often 120–140 °C (Class F insulation)
Sleeve bearing temperature60–85 °C; alarm about 90–95 °C
Insulation resistance, 500 V megger1 MΩ floor; healthy tens to hundreds of MΩ; polarization index 2 or more
Space heateron when stopped, off when running

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Set at speed, voltage a few volts or zeroHz; AVR fuses and supply; excitation switchResidual magnetism lost; AVR failed; exciter field open; diode bridge shortedFuses and wiring, then flash the field per maker; test diodes
Over-voltage, or over-voltage trip, set aloneSensing fuses and wiringSensing lost — AVR sees zero and goes full on; AVR failed; setpoint run upStandby set on; replace fuse or AVR; run it only in parallel until proven
Voltage swings alone at load, steady in parallelWhen the AVR was changedReplacement AVR gain and stability not set up; loose sensing wireRun only in parallel; set up per maker with someone in the ECR
Voltage sags with load, normal at no loadHz first; AVR outputEngine slowing — under-frequency roll-off; open diode; AVR at its ceiling; droop set too highFix the speed first; trend excitation; test diodes
kVAr or PF unequal at equal kWAVR setpoints; droop settingsSetpoints differ; droop pots differ; sensing or CT fault on one setTrim AVR raise/lower until PFs match; set droop equal
kVAr sharing goes wrong when a set is added or removedWhich set changedCross-current loop not shorted or not opened by the breaker auxiliary contact; CT reversedCheck the auxiliary contact and CT wiring — engineer job
kW split uneven, worse on big load changesGovernor modes and droopDroop differs; one isochronous, one droop, no load-share linkTrim governors; set equal droop (see Starting, Reversing, Governors, and Control)
Breaker closes, set won't take kWGovernor raise; mode; fuel limitGovernor motor or raise signal dead; load limit set low; auto-sync trim faultRaise by hand; bring it slightly fast and back to auto
PF leading on one set, its amps rising, bus volts fallingThat set's kVAr meterExcitation lost — AVR failed low, diode short, exciter openOpen that set's breaker if AVR raise does nothing
Winding temperature high at normal loadPhase amps; kVAr; air filterBlocked filter or louvre; high kVAr; hot engine room; unbalanced phasesClean filter; even kVAr; balance loads
One RTD high or open, the others normal, amps balancedRTD reading against its spareRTD or its wiring, junction boxSwitch to the spare element; fix wiring
Bearing temperature risingOil flow sight glass; oil levelLube oil supply lost; oil ring stuck; shaft current through a failed insulated bearing; misalignmentUnload and stop if rising; restore oil before restart
Insulation resistance down on a stopped setSpace heater actually warm; what got wetHeater failed; water ingress or spray; oil and carbon dust on windingsHeater on, dry out, clean; megger again before starting
Space heater on while running, or off while stoppedBreaker or running-signal auxiliary contactContact or heater contactor stuck; heater element openFix the interlock; clamp the heater current