The fuel plant takes bunkers aboard, stores them, cleans them, heats them, and delivers them to the main engine, generators, and boiler at the viscosity and pressure the injection equipment needs. Everything between the manifold and the injectors exists to remove water and solids and to control temperature.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Storage tank in use, HFO / VLSFO | 40–60 °C per bunker report; never below pour point + 10 °C |
| Storage tank going on line | Heated a day ahead; VLSFO ≥ 30 °C |
| Settling tank, HFO | 60–80 °C |
| Service tank, HFO | 80–95 °C |
| Purifier inlet, HFO / VLSFO | 85–98 °C per bunker report, held within 2 °C |
| Purifier inlet, MDO / MGO | Unheated to 40–50 °C |
| Purifier feed rate, HFO | 20–50 % of nameplate |
| Purifier back pressure | 1.5–2.5 bar |
| Booster pressure at engine inlet | 7–10 bar |
| Viscosity at engine inlet, HFO / VLSFO | 10–15 cSt |
| Viscosity at engine inlet, MGO | ≥ 2 cSt; aim for 3 |
| Fine filter ΔP | 0.1–0.3 bar clean; alarm 0.5–1.0 bar |
| Generator knife-edge strainer element | About 500 h |
| Temperature change during changeover | ≤ 2 °C/min |
The plant, stop by stop, as the book walks it.
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Fine filter ΔP rising fast | Purifier; tank in service | Incompatible blend; cat fines; sediment | Bypass in; slow feed; spot test |
| Generator low fuel pressure after changeover | Knife-edge strainer | Loosened sludge; strainer not turned | Turn it; change element, three valves shut |
| Leak-off alarm | Refill rate of the box | Drain clogged; HP component leaking | Flush drain; fast refill — find the leak |
| Viscosity high at engine inlet | Heater outlet temp; steam valve | Steam low; trap; heater fouled | Viscotherm to manual; standby heater |
| Booster pressure hunting | Service tank level; vent | Gas in loop; suction leak; MGO hot | Vent; raise level; cooler on |
| Purifier break-over line warm | Shot timer, then sight port | Seal lost; or a shot just made | Stop feed; remake seal; check disc |
| Purifier high-pressure trip at start | Return valve | Return to tank shut | Line up; restart |
| Purifier won't discharge | Operating water pressure | Strainer; carboned passages; nozzle | Manual shot; strip bowl |
| Water at settler kick mid-transfer | Source tank | Overflow tank unsounded; coil leak | Stop transfer and purifier; call the engineer in charge |
| Transfer pump at full vacuum | Valve at override; tank temp | Valve stuck; cold fuel; vent | Prove valve; heat tank |
| Transfer pump won't pick up after stripping | Pump vent | Lost prime | Bleed to solid fuel |
| Remote tank valve won't move | Control air | Moisture; actuator seized | Cycle air; manual override |
| TLI and sounding disagree | Sounding; vent | Dead band; tank pressurized | Report soundings |
| Flow meter and soundings disagree | Temps, trim, returns | No VCF; returns not subtracted; bypass | Recalculate; seal bypass |
Work out what you’d do, then open it.
The plant went from MGO to VLSFO this morning. In the afternoon a generator alarms low fuel pressure; by evening two others alarm on leak-off. What is happening?
The changeover loosened sludge, and it is arriving at the narrowest points. Turn every generator strainer now and several times a watch for the next day; change a choked element with three valves shut. Time each leak-off box refill before clearing its drain — fast is an HP leak, not sludge. Watch the main engine autofilter for the same cause.
The new bunker goes on top of the old grade in the settler, and the purifier stays at the old temperature. Over a day the bowl packs, shots go soft, and filter ΔP climbs. What should have happened?
Two fuels went through the bowl at a temperature right for neither. Now: clean the bowl, spot test, slow the feed. The change should have followed the grade-change routine in Stop 5, so old and new never met in the bowl.
The next tank is a wing tank. Sea temperature has dropped, coils are full on, the tank reads 25 °C, and the transfer pump goes to full vacuum. What now?
Stay on the current tank; prove the suction valve open at its override. Coils cannot beat cold sea and ballast, so recirculate the tank through a transfer pump and heater until VLSFO is at least 30 °C. That takes 6–8 hours, which is the lesson: watch sea temperature along the route and heat the next tank a day early.
During a drill the release station for the engine room fuel tanks is operated without warning the engine room. What stops, in what order, and how do you get it back?
Service tank outlets shut. Supply pumps lose suction within a minute, booster pressure collapses, and the main engine stops on low fuel pressure; the generators share the service tanks on most ships, so they follow and the ship blacks out. The emergency generator runs on its own tank. Recovery is at the valves: reset every QCV by hand, restore release air, start supply and booster pumps, vent, restart generators, then the main engine.