Part I · The Plants

Fuel Plant

The fuel plant takes bunkers aboard, stores them, cleans them, heats them, and delivers them to the main engine, generators, and boiler at the viscosity and pressure the injection equipment needs. Everything between the manifold and the injectors exists to remove water and solids and to control temperature.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Storage tank in use, HFO / VLSFO40–60 °C per bunker report; never below pour point + 10 °C
Storage tank going on lineHeated a day ahead; VLSFO ≥ 30 °C
Settling tank, HFO60–80 °C
Service tank, HFO80–95 °C
Purifier inlet, HFO / VLSFO85–98 °C per bunker report, held within 2 °C
Purifier inlet, MDO / MGOUnheated to 40–50 °C
Purifier feed rate, HFO20–50 % of nameplate
Purifier back pressure1.5–2.5 bar
Booster pressure at engine inlet7–10 bar
Viscosity at engine inlet, HFO / VLSFO10–15 cSt
Viscosity at engine inlet, MGO≥ 2 cSt; aim for 3
Fine filter ΔP0.1–0.3 bar clean; alarm 0.5–1.0 bar
Generator knife-edge strainer elementAbout 500 h
Temperature change during changeover≤ 2 °C/min

The tour

The plant, stop by stop, as the book walks it.

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Fine filter ΔP rising fastPurifier; tank in serviceIncompatible blend; cat fines; sedimentBypass in; slow feed; spot test
Generator low fuel pressure after changeoverKnife-edge strainerLoosened sludge; strainer not turnedTurn it; change element, three valves shut
Leak-off alarmRefill rate of the boxDrain clogged; HP component leakingFlush drain; fast refill — find the leak
Viscosity high at engine inletHeater outlet temp; steam valveSteam low; trap; heater fouledViscotherm to manual; standby heater
Booster pressure huntingService tank level; ventGas in loop; suction leak; MGO hotVent; raise level; cooler on
Purifier break-over line warmShot timer, then sight portSeal lost; or a shot just madeStop feed; remake seal; check disc
Purifier high-pressure trip at startReturn valveReturn to tank shutLine up; restart
Purifier won't dischargeOperating water pressureStrainer; carboned passages; nozzleManual shot; strip bowl
Water at settler kick mid-transferSource tankOverflow tank unsounded; coil leakStop transfer and purifier; call the engineer in charge
Transfer pump at full vacuumValve at override; tank tempValve stuck; cold fuel; ventProve valve; heat tank
Transfer pump won't pick up after strippingPump ventLost primeBleed to solid fuel
Remote tank valve won't moveControl airMoisture; actuator seizedCycle air; manual override
TLI and sounding disagreeSounding; ventDead band; tank pressurizedReport soundings
Flow meter and soundings disagreeTemps, trim, returnsNo VCF; returns not subtracted; bypassRecalculate; seal bypass

Scenarios

Work out what you’d do, then open it.

low fuel pressure after a changeover

The plant went from MGO to VLSFO this morning. In the afternoon a generator alarms low fuel pressure; by evening two others alarm on leak-off. What is happening?

The changeover loosened sludge, and it is arriving at the narrowest points. Turn every generator strainer now and several times a watch for the next day; change a choked element with three valves shut. Time each leak-off box refill before clearing its drain — fast is an HP leak, not sludge. Watch the main engine autofilter for the same cause.

mixed bunkers cook a purifier

The new bunker goes on top of the old grade in the settler, and the purifier stays at the old temperature. Over a day the bowl packs, shots go soft, and filter ΔP climbs. What should have happened?

Two fuels went through the bowl at a temperature right for neither. Now: clean the bowl, spot test, slow the feed. The change should have followed the grade-change routine in Stop 5, so old and new never met in the bowl.

cold wing tank on a winter crossing

The next tank is a wing tank. Sea temperature has dropped, coils are full on, the tank reads 25 °C, and the transfer pump goes to full vacuum. What now?

Stay on the current tank; prove the suction valve open at its override. Coils cannot beat cold sea and ballast, so recirculate the tank through a transfer pump and heater until VLSFO is at least 30 °C. That takes 6–8 hours, which is the lesson: watch sea temperature along the route and heat the next tank a day early.

quick-closing valves released

During a drill the release station for the engine room fuel tanks is operated without warning the engine room. What stops, in what order, and how do you get it back?

Service tank outlets shut. Supply pumps lose suction within a minute, booster pressure collapses, and the main engine stops on low fuel pressure; the generators share the service tanks on most ships, so they follow and the ship blacks out. The emergency generator runs on its own tank. Recovery is at the valves: reset every QCV by hand, restore release air, start supply and booster pumps, vent, restart generators, then the main engine.

Dependencies

Needs
  • Electrical — pumps, purifiers, heaters, viscotherm, automatic filter
  • Steam or electric heating — tanks, heaters, tracing; on HFO, no heat means no fuel within hours
  • Compressed air — dry control air for remote tank valves and steam control valves; QCV release on pneumatic systems
  • LT cooling water — MGO cooler
  • Freshwater — purifier operating and sealing water
Feeds
  • Main engine
  • Diesel generators
  • Auxiliary boiler
  • Incinerator
  • Emergency generator, by its own tank filled from this plant