Fire protection is three systems at one control station: water (fire pumps and a fire main feeding hydrants, sprinklers, and the shore connection), a fixed gas or mist system in the machinery space, and detection with the shutdowns that go with it. The engineer keeps the pumps, the main, the fixed system, and the shutdowns ready; the whole crew uses them.
Lessons teach one thing step by step. Simulators are free play: best after the lesson.
Maker’s values override these.
| Point | Typical |
|---|---|
| Fire main at pump discharge, pump running | 6–10 bar |
| Pressure at the two furthest hydrants, two jets flowing | ≥ 2.5–2.7 bar (SOLAS, by tonnage) |
| Jockey (pressurizing) pump cut-in / cut-out | 5–6 / 8–9 bar |
| Emergency fire pump capacity | ≥ 40 % of total required, never < 25 m³/h |
| Emergency fire pump priming from dry | under 1–2 min; log yours |
| Emergency fire pump diesel fuel | 3 h at full load |
| Emergency fire pump priming pot | about ¾ full |
| Counterweight fire damper, counts as shut | lever ≥ ¾ of its travel to the stop |
| CO₂ cylinders | 45 kg in a 67.5 L cylinder; recharge below 90 % contents |
| CO₂ discharge, machinery space | 85 % of gas in ≤ 2 min; 40 % of space volume |
| Pre-discharge alarm before gas flows | 20–60 s, ship specific |
| Detector testing | every head within a year |
The plant, stop by stop, as the book walks it.
Each one is a set of readings. Decide what they mean and what you’d check first, then look.
| Symptom | Check first | Likely causes | Action |
|---|---|---|---|
| Fire main pressure falls with pumps stopped | Shut the ER isolation valve; does it still fall? | Fire pump overboard valve leaking by after GS use; hydrant or hose weeping; deck-wash open; pump check valve passing | Isolate by section until it holds; walk that section |
| Jockey pump cycling constantly | Time the fall with it stopped | Small leak; switch differential narrow; jockey check valve passing | Find the leak; reset the switch |
| Fire pump running, discharge low, amps low | Suction vacuum; strainer | Strainer blocked; sea chest valve; air at the gland | Clean; open; repack |
| Fire pump running, ejector still noisy, pressure low | Feel the discharge pipe | Not primed; air at the suction | Stop; check priming air and suction lineup; restart |
| Fire pump won't start on switch or remote | Selector in auto; starter | Setpoint; starter; remote circuit | Start by hand; fix before UMS |
| Emergency fire pump: vacuum builds, no water | Sea suction valve by hand | Valve closed; strainer packed; foot valve stuck | Open; clean; free the valve |
| Emergency fire pump runs, no pressure | Priming pot; priming clutch | Pot empty; clutch not engaged | Fill the pot; kick the clutch handle; retest |
| Emergency fire pump: no vacuum | Priming pump sealing water; suction joints | Air leak; priming pump worn; priming lineup | Soap test under vacuum; repair |
| Emergency diesel won't start | Battery, fuel, stop lever | Flat battery; no fuel; cold; lever not reset | Fix now — it is the only pump outside the ER |
| Low pressure at a far hydrant, two jets | Isolation valves along the run | Valve partly closed; blocked section; too many consumers open | Open fully; shut other consumers; flush |
| Detection panel fault, one zone | Fault log; last work on that loop | Head removed; wet junction box; chafed cable; dirty head | Fix the loop; man the ER if it is a machinery zone |
| Repeated alarm from one head, nothing found | What happens there at that time | Steam, dust, exhaust; aged head | Clean or replace; relocate or change type |
| CO₂ room gas alarm, or cylinders below level | Leak detector at the discharge heads | Head seals seeping; short fill | Ventilate; tag and recharge |
| Damper pointer says closed, air still flowing | Blade by hand; counterweight travel | Blade sheared from shaft; linkage slipped; weight short of its stop | Repair; test every damper weekly |
| Quick-closing valve won't close on release | Release pressure; valve stem | Release line leaked down; stem seized | Free the stem; restore pressure; retest |
Work out what you’d do, then open it.
Since a fire pump was used yesterday to strip a tank overboard, the fire main will not hold pressure: 7 bar with the jockey pump stopped at 2200, 2 bar by 0600. No water on deck. Where is it going?
No wet deck means to sea. The first suspect is the pump just used: its overboard valve, not closed tight after the job, is passing the main back over the side. Close it hard and repeat the fall test. If it still falls, shut the machinery space isolation valve with the jockey pump stopped; holding now points to a stopped pump's check valve — feel each casing for flow. Still falling, shut deck sections one at a time until it holds and walk that section. Afterwards, check the pump's lineup is back to fire duty.
Weekly test. The bridge has been called and the anchor wash bleeder is open. The pump runs at speed, but the discharge gauge sits near zero and the discharge pipe is warm. What is wrong?
It has lost prime and is churning water in the casing. Check the priming pot first — keep it about ¾ full — then the priming pump clutch: kick the handle to seat the pulley on the shaft. Priming is done when the priming discharge stops and the drive disengages; then pressure comes up and the pipe runs cool. If it still will not prime, check the sea suction by hand and soap-test the suction joints. Do not sail with this open: the whole point of the pump is that it works without the engine room.
0300, UMS, engine room unattended. The panel shows a fault on the machinery space zone covering the generator flat. No alarm. The duty engineer asks whether to isolate the zone so the buzzer stops and go back to bed. Answer?
No. A fault is the panel saying it cannot see that zone. Isolating it changes nothing but the noise, and it removes the one condition that lets the engine room be unattended. The engine room is manned from now until the loop is fixed — that is what changes, and it changes the watch rota tonight. Call the ETO; most zone faults are a head unscrewed, a wet junction box, or a cable chafed where someone worked yesterday. Log the fault, the manning change, and the fix, and tell the bridge, because the master decides when the ship goes back to unattended operation.
Fire in the purifier flat, hoses are not holding it, and the master has ordered the machinery space CO₂ released. What is the engineer's sequence, and what stops in what order?
People, then air, then fuel, then gas. Confirm by head count at the muster — everyone out of the space, including whoever went back for something. Stop the fans and close every damper, skylight, and casing door; the gas is useless if the space breathes. Pull the quick-closing valves, hit the fuel pump stops, stop the main engine. The generators in the space stop with their fuel, so the emergency generator must be running and the emergency fire pump is now your only fire pump — line it up before the lights go. Then the release: distribution valve for the space, then the bank, from the release cabinet, and confirm by sound and the manifold gauge that gas went. The space stays shut and the boundaries get cooled from outside until they stop rising — hours, not minutes. Restoring later starts from the list of everything the release tripped.