Part I · The Plants

Fire Protection

Fire protection is three systems at one control station: water (fire pumps and a fire main feeding hydrants, sprinklers, and the shore connection), a fixed gas or mist system in the machinery space, and detection with the shutdowns that go with it. The engineer keeps the pumps, the main, the fixed system, and the shutdowns ready; the whole crew uses them.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Fire main at pump discharge, pump running6–10 bar
Pressure at the two furthest hydrants, two jets flowing≥ 2.5–2.7 bar (SOLAS, by tonnage)
Jockey (pressurizing) pump cut-in / cut-out5–6 / 8–9 bar
Emergency fire pump capacity≥ 40 % of total required, never < 25 m³/h
Emergency fire pump priming from dryunder 1–2 min; log yours
Emergency fire pump diesel fuel3 h at full load
Emergency fire pump priming potabout ¾ full
Counterweight fire damper, counts as shutlever ≥ ¾ of its travel to the stop
CO₂ cylinders45 kg in a 67.5 L cylinder; recharge below 90 % contents
CO₂ discharge, machinery space85 % of gas in ≤ 2 min; 40 % of space volume
Pre-discharge alarm before gas flows20–60 s, ship specific
Detector testingevery head within a year

The tour

The plant, stop by stop, as the book walks it.

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Fire main pressure falls with pumps stoppedShut the ER isolation valve; does it still fall?Fire pump overboard valve leaking by after GS use; hydrant or hose weeping; deck-wash open; pump check valve passingIsolate by section until it holds; walk that section
Jockey pump cycling constantlyTime the fall with it stoppedSmall leak; switch differential narrow; jockey check valve passingFind the leak; reset the switch
Fire pump running, discharge low, amps lowSuction vacuum; strainerStrainer blocked; sea chest valve; air at the glandClean; open; repack
Fire pump running, ejector still noisy, pressure lowFeel the discharge pipeNot primed; air at the suctionStop; check priming air and suction lineup; restart
Fire pump won't start on switch or remoteSelector in auto; starterSetpoint; starter; remote circuitStart by hand; fix before UMS
Emergency fire pump: vacuum builds, no waterSea suction valve by handValve closed; strainer packed; foot valve stuckOpen; clean; free the valve
Emergency fire pump runs, no pressurePriming pot; priming clutchPot empty; clutch not engagedFill the pot; kick the clutch handle; retest
Emergency fire pump: no vacuumPriming pump sealing water; suction jointsAir leak; priming pump worn; priming lineupSoap test under vacuum; repair
Emergency diesel won't startBattery, fuel, stop leverFlat battery; no fuel; cold; lever not resetFix now — it is the only pump outside the ER
Low pressure at a far hydrant, two jetsIsolation valves along the runValve partly closed; blocked section; too many consumers openOpen fully; shut other consumers; flush
Detection panel fault, one zoneFault log; last work on that loopHead removed; wet junction box; chafed cable; dirty headFix the loop; man the ER if it is a machinery zone
Repeated alarm from one head, nothing foundWhat happens there at that timeSteam, dust, exhaust; aged headClean or replace; relocate or change type
CO₂ room gas alarm, or cylinders below levelLeak detector at the discharge headsHead seals seeping; short fillVentilate; tag and recharge
Damper pointer says closed, air still flowingBlade by hand; counterweight travelBlade sheared from shaft; linkage slipped; weight short of its stopRepair; test every damper weekly
Quick-closing valve won't close on releaseRelease pressure; valve stemRelease line leaked down; stem seizedFree the stem; restore pressure; retest

Scenarios

Work out what you’d do, then open it.

pressure won't hold

Since a fire pump was used yesterday to strip a tank overboard, the fire main will not hold pressure: 7 bar with the jockey pump stopped at 2200, 2 bar by 0600. No water on deck. Where is it going?

No wet deck means to sea. The first suspect is the pump just used: its overboard valve, not closed tight after the job, is passing the main back over the side. Close it hard and repeat the fall test. If it still falls, shut the machinery space isolation valve with the jockey pump stopped; holding now points to a stopped pump's check valve — feel each casing for flow. Still falling, shut deck sections one at a time until it holds and walk that section. Afterwards, check the pump's lineup is back to fire duty.

emergency fire pump won't build pressure

Weekly test. The bridge has been called and the anchor wash bleeder is open. The pump runs at speed, but the discharge gauge sits near zero and the discharge pipe is warm. What is wrong?

It has lost prime and is churning water in the casing. Check the priming pot first — keep it about ¾ full — then the priming pump clutch: kick the handle to seat the pulley on the shaft. Priming is done when the priming discharge stops and the drive disengages; then pressure comes up and the pipe runs cool. If it still will not prime, check the sea suction by hand and soap-test the suction joints. Do not sail with this open: the whole point of the pump is that it works without the engine room.

zone fault — isolate or not?

0300, UMS, engine room unattended. The panel shows a fault on the machinery space zone covering the generator flat. No alarm. The duty engineer asks whether to isolate the zone so the buzzer stops and go back to bed. Answer?

No. A fault is the panel saying it cannot see that zone. Isolating it changes nothing but the noise, and it removes the one condition that lets the engine room be unattended. The engine room is manned from now until the loop is fixed — that is what changes, and it changes the watch rota tonight. Call the ETO; most zone faults are a head unscrewed, a wet junction box, or a cable chafed where someone worked yesterday. Log the fault, the manning change, and the fix, and tell the bridge, because the master decides when the ship goes back to unattended operation.

CO₂ release ordered

Fire in the purifier flat, hoses are not holding it, and the master has ordered the machinery space CO₂ released. What is the engineer's sequence, and what stops in what order?

People, then air, then fuel, then gas. Confirm by head count at the muster — everyone out of the space, including whoever went back for something. Stop the fans and close every damper, skylight, and casing door; the gas is useless if the space breathes. Pull the quick-closing valves, hit the fuel pump stops, stop the main engine. The generators in the space stop with their fuel, so the emergency generator must be running and the emergency fire pump is now your only fire pump — line it up before the lights go. Then the release: distribution valve for the space, then the bank, from the release cabinet, and confirm by sound and the manifold gauge that gas went. The space stays shut and the boundaries get cooled from outside until they stop rising — hours, not minutes. Restoring later starts from the list of everything the release tripped.

Dependencies

Needs
  • Electrical, main switchboard — main fire pumps, jockey pump, water mist pump unit
  • Emergency switchboard or an independent diesel — emergency fire pump; detection panel after its battery; control station lighting
  • Seawater suction — sea chests and strainers for every fire pump (see Seawater and Central Cooling, stops 1–2)
  • The boiler feed or distillate tank — water mist supply on some ships
  • Compressed air or hydraulic pressure — quick-closing valve release and actuated dampers where fitted (see Compressed Air, stop 8)
  • Nothing, for CO₂ release — mechanical and pilot gas by design
Feeds
  • The ship's survival in a fire, and the fire control plan the whole crew drills to
  • Unattended machinery space operation — lost the moment detection is unserviceable
  • Hot work — no permit without a working detection zone and a charged main
  • Deck-wash and anchor-wash branches off the fire main
  • Port state and class — a fire pump, fixed system, or detection defect is a detainable item