Part II · The Equipment · Family 1 · Move It · Stage 3 · First hitch

Fans and Blowers

Fans move air at low pressure: combustion and ventilation air into the engine room, fumes and heat out of the spaces that make them, conditioned air through the accommodation. Almost every fan fault shows first as vibration, a change in amps, or a space hotter or smellier than yesterday.

Lessons and simulators

Lessons teach one thing step by step. Simulators are free play: best after the lesson.

What kills it

Normal numbers

Maker’s values override these.

PointTypical
Motor amps, fan running normally70–90 % of nameplate, steady
Vibration on the bearing housing (ISO 10816 guide)under 4.5 mm/s good · 7 mm/s investigate · 11 mm/s stop
Bearing housing temperatureambient + 20–40 °C; too hot to hold a hand on means check it with the IR gun
Belt deflection, mid-span, firm thumbabout 15 mm per meter of span
Belt re-tension after renewalafter 24–48 h of running
Engine room pressure, hatches closedslightly positive; doors open normally
Boiler pre-purge30–90 s, air damper fully open (see Steam, Stop 2)
Fire damper, counterweight type, shutlever traveled at least ¾ of the way to the stop
ME auxiliary blowersrunning below roughly 30–40 % load; auto start/stop on scavenge pressure

Reading the gauges

Each one is a set of readings. Decide what they mean and what you’d check first, then look.

Symptoms

SymptomCheck firstLikely causesAction
Vibration new or risingMount bolts; blade foulingUnbalance from dirt or a bent blade; bearing failing; belt or sheave; cracked mountStop; clean; inspect; balance
Amps low, air low, sound normalRotation arrow; beltReversed after motor work; belt slipping; damper closedSwap two phases; tension or renew belts
Axial fan amps high, roaring or surgingDampers and louvres on that trunkStall — fire damper dropped, damper closed, screen fouled, duct blockedOpen the path; then clean
Forward-curved AHU fan trips on overload after workFilters and access doorFilters out or wrong size; door open; duct disconnectedRestore the resistance; reset
Squeal at start; black dust under the guardBelt tension; sheave alignmentLoose, glazed, or oily belts; misaligned or worn sheavesRenew as a set; straightedge across both sheaves
Bearing hotGrease; belt tensionOver- or under-greased; over-tensioned belts; misalignmentCorrect; renew bearing if noise stays
Fan running, space still hot or smellingDampers in that ductFire damper closed; backdraught damper stuck; duct blocked; reversed rotationHand at the outlet; walk the duct
ER doors hard to open, hatches shutFans running vs loadToo many supply fans for the exhaust and engine demandStop one supply fan
Boiler locks out at pre-purgeDamper travel; air pressure switchFD fan not proven — belt slipping, damper limit switch, blocked impulse lineWatch the damper move; see Steam, Stop 2
Aux blowers start and stop every few minutesEngine load and turbo speedScavenge pressure sitting in the switching bandBlowers to manual until load rises; back to auto
Fan won't restart after a blackout or CO₂ testInterlock and restart listNot on the sequential restart; ventilation stop still latched; damper interlockReset the stop; restart by hand